More actions
(probably the most DETAILED RECAPP.) |
No edit summary |
||
(2 intermediate revisions by 2 users not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: EST QuickStart QSC <br />FACP Location: Caretaker’s Office <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2012 <br />Year Opened: 1993 | | FACP: EST QuickStart QSC <br />FACP Location: Caretaker’s Office <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2012 <br />Year Opened: 1993 | ||
|} | |} | ||
'''Monsignor A. J. Hetherington School''' is a catholic elementary school located at 4 Coral Springs Blvd NE, Calgary, AB. It is part of the Calgary Catholic School District, teaches grades K-6 and has an enrollment of about 300 students. It was built in 1994, and the fire alarm system was upgraded in 2012; the pull stations are original. | '''Monsignor A. J. Hetherington School''' is a catholic elementary school located at 4 Coral Springs Blvd NE, Calgary, AB. It is part of the Calgary Catholic School District, teaches grades K-6 and has an enrollment of about 300 students. It was built in 1994, and the fire alarm system was upgraded in 2012; the pull stations are original. | ||
== System Specifications (2012-present) == | == System Specifications (2012-present) == | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by an EST QuickStart QSC conventional fire alarm system. The panel is located in the caretaker’s office. The system coding is temporal. | The building is protected by an EST QuickStart QSC conventional fire alarm system. The panel is located in the caretaker’s office. The system coding is temporal. | ||
===== Annunciators ===== | ===== Annunciators ===== | ||
There is an EST QSA-1-S cabinet with a QSC-CPU-1 LCD annunciator and SL30 LED annunciator in the main entrance vestibule. | There is an EST QSA-1-S cabinet with a QSC-CPU-1 LCD annunciator and SL30 LED annunciator in the main entrance vestibule. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All indoor notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). <br> For exterior notification, there are EST “Integrity” 757-8A-T horn/strobes (red, wall-mount, 110cd). | All indoor notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). <br> For exterior notification, there are EST “Integrity” 757-8A-T horn/strobes (red, wall-mount, 110cd). | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are the original Edwards 270-SPO conventional single-action pull stations. | |||
All pull stations are the original Edwards 270-SPO conventional pull stations. | |||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the building. <br> There are Edwards EC20RRU-3 fixed/rate-of-rise heat detectors in some areas; these replaced Edwards 281C fixed/rate-of-rise heat detectors after being recalled. <br> There are also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired to 6262B-001 test stations/alarm indicators. | |||
There are Edwards | ==== EOLs ==== | ||
There are Edwards EOL-P1 end of line resistor plates on all circuits. | |||
== Former System Specifications (1994-2012) == | == Former System Specifications (1994-2012) == | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 42: | Line 31: | ||
| | | | ||
|- | |- | ||
| FACP: EST ESA2000 <br />FACP Location: Caretaker’s Office <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br /> Year Installed: 1994 <br />Year Decommissioned: 2012 | | FACP: EST ESA2000 <br />FACP Location: Caretaker’s Office <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br /> Year Installed: 1994 <br />Year Decommissioned: 2012 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building was protected by an EST ESA2000 conventional fire alarm system. The panel was located in the caretaker’s office. The system coding was continuous. | The building was protected by an EST ESA2000 conventional fire alarm system. The panel was located in the caretaker’s office. The system coding was continuous. | ||
===== Annunciators ===== | ===== Annunciators ===== | ||
There was an EST annunciator in the main entrance vestibule, model to be confirmed. | There was an EST annunciator in the main entrance vestibule, model to be confirmed. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
Most notification appliances were Wheelock MBS-G6-24 motor bell/strobes (6” gong, 1.5cd). <br> The gymnasium had Wheelock MBS-G10-24 motor bell/strobes (10” gong, 1.5cd) due to higher ambient noise levels. <br> For exterior notification, there were Edwards 439D-6AWC vibrating bells (6” gong). | Most notification appliances were Wheelock MBS-G6-24 motor bell/strobes (6” gong, 1.5cd). <br> The gymnasium had Wheelock MBS-G10-24 motor bell/strobes (10” gong, 1.5cd) due to higher ambient noise levels. <br> For exterior notification, there were Edwards 439D-6AWC vibrating bells (6” gong). | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations were Edwards 270-SPO conventional pull stations, these are still in service. | |||
==== Automatic Detection Devices ==== | |||
There were Edwards 6250C conventional ionization smoke detectors throughout the building. | |||
There were Edwards 281C fixed/rate-of-rise heat detectors in some areas, these remained on the current system until 2020. | |||
There were also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired up to 6262B-001 test stations/alarm indicators, these remain. | |||
There were Edwards | ==== EOLs ==== | ||
There were Edwards EOL-P1 end of line resistor plates on all circuits. | |||
[[Category:Calgary]] | |||
[[Category:Schools]] |
Latest revision as of 14:19, 13 October 2024
System Specifications |
---|
FACP: EST QuickStart QSC FACP Location: Caretaker’s Office System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, EST Date of last known Upgrade: 2012 Year Opened: 1993 |
Monsignor A. J. Hetherington School is a catholic elementary school located at 4 Coral Springs Blvd NE, Calgary, AB. It is part of the Calgary Catholic School District, teaches grades K-6 and has an enrollment of about 300 students. It was built in 1994, and the fire alarm system was upgraded in 2012; the pull stations are original.
System Specifications (2012-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by an EST QuickStart QSC conventional fire alarm system. The panel is located in the caretaker’s office. The system coding is temporal.
Annunciators[edit | edit source]
There is an EST QSA-1-S cabinet with a QSC-CPU-1 LCD annunciator and SL30 LED annunciator in the main entrance vestibule.
Notification Appliances[edit | edit source]
All indoor notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).
For exterior notification, there are EST “Integrity” 757-8A-T horn/strobes (red, wall-mount, 110cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are the original Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the building.
There are Edwards EC20RRU-3 fixed/rate-of-rise heat detectors in some areas; these replaced Edwards 281C fixed/rate-of-rise heat detectors after being recalled.
There are also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired to 6262B-001 test stations/alarm indicators.
EOLs[edit | edit source]
There are Edwards EOL-P1 end of line resistor plates on all circuits.
Former System Specifications (1994-2012)[edit | edit source]
System Specifications |
---|
FACP: EST ESA2000 FACP Location: Caretaker’s Office System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Installed: 1994 Year Decommissioned: 2012 |
FACP[edit | edit source]
The building was protected by an EST ESA2000 conventional fire alarm system. The panel was located in the caretaker’s office. The system coding was continuous.
Annunciators[edit | edit source]
There was an EST annunciator in the main entrance vestibule, model to be confirmed.
Notification Appliances[edit | edit source]
Most notification appliances were Wheelock MBS-G6-24 motor bell/strobes (6” gong, 1.5cd).
The gymnasium had Wheelock MBS-G10-24 motor bell/strobes (10” gong, 1.5cd) due to higher ambient noise levels.
For exterior notification, there were Edwards 439D-6AWC vibrating bells (6” gong).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Edwards 270-SPO conventional pull stations, these are still in service.
Automatic Detection Devices[edit | edit source]
There were Edwards 6250C conventional ionization smoke detectors throughout the building.
There were Edwards 281C fixed/rate-of-rise heat detectors in some areas, these remained on the current system until 2020.
There were also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired up to 6262B-001 test stations/alarm indicators, these remain.
EOLs[edit | edit source]
There were Edwards EOL-P1 end of line resistor plates on all circuits.