Line 5: Line 5:
|  
|  
|-
|-
| FACP: EST QuickStart QSC <br />FACP Location: Caretaker’s Office <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2012 <br />Year Opened: 1993
| FACP: EST QuickStart QSC <br />FACP Location: Caretaker’s Office <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2012 <br />Year Opened: 1993
|}
|}
'''Monsignor A. J. Hetherington School''' is a catholic elementary school located at 4 Coral Springs Blvd NE, Calgary, AB. It is part of the Calgary Catholic School District, teaches grades K-6 and has an enrollment of about 300 students. It was built in 1994, and the fire alarm system was upgraded in 2012; the pull stations are original.
'''Monsignor A. J. Hetherington School''' is a catholic elementary school located at 4 Coral Springs Blvd NE, Calgary, AB. It is part of the Calgary Catholic School District, teaches grades K-6 and has an enrollment of about 300 students. It was built in 1994, and the fire alarm system was upgraded in 2012; the pull stations are original.
== System Specifications (2012-present) ==
== System Specifications (2012-present) ==
==== FACP ====
==== FACP ====
The building is protected by an EST QuickStart QSC conventional fire alarm system. The panel is located in the caretaker’s office. The system coding is temporal.
The building is protected by an EST QuickStart QSC conventional fire alarm system. The panel is located in the caretaker’s office. The system coding is temporal.
===== Annunciators =====
===== Annunciators =====
There is an EST QSA-1-S cabinet with a QSC-CPU-1 LCD annunciator and SL30 LED annunciator in the main entrance vestibule.  
There is an EST QSA-1-S cabinet with a QSC-CPU-1 LCD annunciator and SL30 LED annunciator in the main entrance vestibule.  
==== Notification Appliances ====
==== Notification Appliances ====
All indoor notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). <br> For exterior notification, there are EST “Integrity” 757-8A-T horn/strobes (red, wall-mount, 110cd).
All indoor notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). <br> For exterior notification, there are EST “Integrity” 757-8A-T horn/strobes (red, wall-mount, 110cd).
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
 
All pull stations are the original Edwards 270-SPO conventional single-action pull stations.
All pull stations are the original Edwards 270-SPO conventional pull stations.
 
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the building. <br> There are Edwards EC20RRU-3 fixed/rate-of-rise heat detectors in some areas; these replaced Edwards 281C fixed/rate-of-rise heat detectors after being recalled. <br> There are also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired to 6262B-001 test stations/alarm indicators.


There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the building. <br> There are Edwards EC20RRU-3 fixed/rate-of-rise heat detectors in some areas; these replaced Edwards 281C fixed/rate-of-rise heat detectors after being recalled. <br> There are also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired up to 6262B-001 test stations/alarm indicators.
==== EOLs ====
There are Edwards EOL-P1 end of line resistor plates on all circuits.


== Former System Specifications (1994-2012) ==
== Former System Specifications (1994-2012) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 42: Line 31:
|  
|  
|-
|-
| FACP: EST ESA2000 <br />FACP Location: Caretaker’s Office <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br /> Year Installed: 1994 <br />Year Decommissioned: 2012
| FACP: EST ESA2000 <br />FACP Location: Caretaker’s Office <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br /> Year Installed: 1994 <br />Year Decommissioned: 2012
|}
|}




==== FACP ====
==== FACP ====
The building was protected by an EST ESA2000 conventional fire alarm system. The panel was located in the caretaker’s office. The system coding was continuous.
The building was protected by an EST ESA2000 conventional fire alarm system. The panel was located in the caretaker’s office. The system coding was continuous.
===== Annunciators =====
===== Annunciators =====
There was an EST annunciator in the main entrance vestibule, model to be confirmed.
There was an EST annunciator in the main entrance vestibule, model to be confirmed.
==== Notification Appliances ====
==== Notification Appliances ====
Most notification appliances were Wheelock MBS-G6-24 motor bell/strobes (6” gong, 1.5cd). <br> The gymnasium had Wheelock MBS-G10-24 motor bell/strobes (10” gong, 1.5cd) due to higher ambient noise levels. <br> For exterior notification, there were Edwards 439D-6AWC vibrating bells (6” gong).
Most notification appliances were Wheelock MBS-G6-24 motor bell/strobes (6” gong, 1.5cd). <br> The gymnasium had Wheelock MBS-G10-24 motor bell/strobes (10” gong, 1.5cd) due to higher ambient noise levels. <br> For exterior notification, there were Edwards 439D-6AWC vibrating bells (6” gong).
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All pull stations were Edwards 270-SPO conventional pull stations, these are still in service.
==== Automatic Detection Devices ====
There were Edwards 6250C conventional ionization smoke detectors throughout the building.


All pull stations were Edwards 270-SPO conventional pull stations, these are still in service.
There were Edwards 281C fixed/rate-of-rise heat detectors in some areas, these remained on the current system until 2020.  


==== Automatic Detection Devices ====
There were also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired up to 6262B-001 test stations/alarm indicators, these remain.


There were Edwards 6250C conventional ionization smoke detectors throughout the building. There were Edwards 281C fixed/rate-of-rise heat detectors in some areas, these remained on the current system until 2020. There were also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired up to 6262B-001 test stations/alarm indicators, these remain.
==== EOLs ====
There were Edwards EOL-P1 end of line resistor plates on all circuits.
[[Category:Calgary]]
[[Category:Schools]]

Latest revision as of 14:19, 13 October 2024

System Specifications
FACP: EST QuickStart QSC
FACP Location: Caretaker’s Office
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2012
Year Opened: 1993

Monsignor A. J. Hetherington School is a catholic elementary school located at 4 Coral Springs Blvd NE, Calgary, AB. It is part of the Calgary Catholic School District, teaches grades K-6 and has an enrollment of about 300 students. It was built in 1994, and the fire alarm system was upgraded in 2012; the pull stations are original.

System Specifications (2012-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by an EST QuickStart QSC conventional fire alarm system. The panel is located in the caretaker’s office. The system coding is temporal.

Annunciators[edit | edit source]

There is an EST QSA-1-S cabinet with a QSC-CPU-1 LCD annunciator and SL30 LED annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

All indoor notification appliances are EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).
For exterior notification, there are EST “Integrity” 757-8A-T horn/strobes (red, wall-mount, 110cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are the original Edwards 270-SPO conventional single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the building.
There are Edwards EC20RRU-3 fixed/rate-of-rise heat detectors in some areas; these replaced Edwards 281C fixed/rate-of-rise heat detectors after being recalled.
There are also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired to 6262B-001 test stations/alarm indicators.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all circuits.

Former System Specifications (1994-2012)[edit | edit source]

System Specifications
FACP: EST ESA2000
FACP Location: Caretaker’s Office
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Installed: 1994
Year Decommissioned: 2012


FACP[edit | edit source]

The building was protected by an EST ESA2000 conventional fire alarm system. The panel was located in the caretaker’s office. The system coding was continuous.

Annunciators[edit | edit source]

There was an EST annunciator in the main entrance vestibule, model to be confirmed.

Notification Appliances[edit | edit source]

Most notification appliances were Wheelock MBS-G6-24 motor bell/strobes (6” gong, 1.5cd).
The gymnasium had Wheelock MBS-G10-24 motor bell/strobes (10” gong, 1.5cd) due to higher ambient noise levels.
For exterior notification, there were Edwards 439D-6AWC vibrating bells (6” gong).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Edwards 270-SPO conventional pull stations, these are still in service.

Automatic Detection Devices[edit | edit source]

There were Edwards 6250C conventional ionization smoke detectors throughout the building.

There were Edwards 281C fixed/rate-of-rise heat detectors in some areas, these remained on the current system until 2020.

There were also Edwards 6266C-001 photoelectric duct smoke detectors in 6260B housings, located throughout the building behind the ceiling tiles, wired up to 6262B-001 test stations/alarm indicators, these remain.

EOLs[edit | edit source]

There were Edwards EOL-P1 end of line resistor plates on all circuits.