More actions
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier AFP-200C <br />FACP Location: Electrical Room <br />System Type: Addressable...") |
(Eye soh lators are annoying) |
||
(One intermediate revision by the same user not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier AFP- | | FACP: Notifier AFP-200 <br />FACP Location: Electrical Room <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: N/A <br />Date of last known Upgrade: N/A <br />Year Opened: 2001 | ||
|} | |} | ||
'''Ecole Poirier Elementary''' is an elementary school located at 6526 Throup Rd, Sooke, BC. The school was built in 2001, and the fire alarm system is original. | |||
'''Ecole Poirier Elementary''' is an elementary school located at 6526 Throup Rd, Sooke, BC. | |||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Notifier AFP-200 addressable fire alarm system. | The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s CLIP addressable protocol, and the system coding is continuous. | ||
=====Annunciators===== | =====Annunciators===== | ||
There is a Notifier ACM-24AT annunciator at the main entrance. | There is a Notifier ACM-24AT annunciator at the main entrance. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
Most notification appliances are Notifier KMS-10-24VDC/P motor bells (10” gong). | Most notification appliances are Notifier KMS-10-24VDC/P motor bells (10” gong). <br>Some areas have Notifier KMS-10-24A motor bells (10” gong) as deficiency replacements. | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Notifier NFM-950B conventional single-action pull stations | All pull stations are Notifier NFM-950B conventional single-action pull stations, wired to Notifier MMX-101A addressable monitor modules. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Notifier CPX-551A addressable ionization smoke detectors throughout the building. <br> Some areas have Notifier FSP-851A addressable photoelectric smoke detectors as deficiency replacements. | There are Notifier CPX-551A addressable ionization smoke detectors throughout the building. <br> Some areas have Notifier FSP-851A addressable photoelectric smoke detectors as deficiency replacements. <br>Some areas have Notifier FDX-551RA addressable 135°F fixed-temperature/rate-of-rise heat detectors. <br>All detectors are mounted on Notifier BX501 bases. | ||
====Modules==== | ====Modules==== | ||
There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
==== EOLs ==== | |||
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits. | |||
[[Category:British Columbia]] | |||
[[Category:Schools]] |
Latest revision as of 19:48, 25 September 2024
System Specifications |
---|
FACP: Notifier AFP-200 FACP Location: Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: N/A Date of last known Upgrade: N/A Year Opened: 2001 |
Ecole Poirier Elementary is an elementary school located at 6526 Throup Rd, Sooke, BC. The school was built in 2001, and the fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s CLIP addressable protocol, and the system coding is continuous.
Annunciators[edit | edit source]
There is a Notifier ACM-24AT annunciator at the main entrance.
Notification Appliances[edit | edit source]
Most notification appliances are Notifier KMS-10-24VDC/P motor bells (10” gong).
Some areas have Notifier KMS-10-24A motor bells (10” gong) as deficiency replacements.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NFM-950B conventional single-action pull stations, wired to Notifier MMX-101A addressable monitor modules.
Automatic Detection Devices[edit | edit source]
There are Notifier CPX-551A addressable ionization smoke detectors throughout the building.
Some areas have Notifier FSP-851A addressable photoelectric smoke detectors as deficiency replacements.
Some areas have Notifier FDX-551RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on Notifier BX501 bases.
Modules[edit | edit source]
There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.