| FACP: Edwards EST3 <br />FACP Location: Electrical Room <br />System Type: Hybrid-Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal? <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2021 <br />Year Opened: 1962
| FACP: Edwards EST3 <br />FACP Location: Electrical Room <br />System Type: Single-Stage Hybrid-Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal? <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2021 <br />Year Opened: 1962
|}
|}




'''Cochrane High School''' is a large high school in Cochrane, Alberta, Canada. The school opened in 1962, and expanded several times: 1966, 1970, 1972, 1985, with a second floor being added in 1991, and finally a modernization in 1996. Portables were installed in 1990 and 1992. The fire alarm system had an upgrade in 2015.  
'''Cochrane High School''' is a large high school located at 529 4th Ave N, Cochrane, Alberta, Canada. The school opened in 1962, and expanded several times: 1966, 1970, 1972, 1985, with a second floor being added in 1991, and finally a modernization in 1996. Portables were installed in 1990 and 1992. The fire alarm system had an upgrade in 2015.  
==System Specifications (1991-present)==
==System Specifications (1991-present)==
====FACP====
====FACP====
Line 16: Line 16:
The panel replaced an Edwards Custom 6500 in 2015, and the system was upgraded to mostly addressable.
The panel replaced an Edwards Custom 6500 in 2015, and the system was upgraded to mostly addressable.
===== Annunciators =====
===== Annunciators =====
There is an Edwards EST 3-LCDXL1 LCD annunciator at the entrance.
There is an Edwards EST 3-LCDANN LCD annunciator in the lobby, with an LCDXL1 display.
====Notification Appliances====
====Notification Appliances====
All notification appliances except for one are Edwards 439D-6AWC vibrating bells (6” gong), installed in 1985 and 1991 depending on the area; these are also in the portables.
All notification appliances except for one are Edwards 439D-6AWC vibrating bells (6” gong), installed in 1991 or 1996 depending on the area; these are also in the portables.


Approximately 70% of bells are mounted on Edwards 403-5A-R strobe plates (15cd), which were added in 1996. The remaining bells are mostly installed remotely, most behind metal grills.  
Approximately 70% of bells are mounted on Edwards 403-5A-R strobe plates (15cd), which were added in 1996. The remaining bells are mostly installed remotely, most behind metal grills.  
Line 27: Line 27:
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are EST SIGA-270 addressable single-action pull stations.  
All pull stations in the main building are EST SIGA-270 addressable single-action pull stations.  


The portables still have their Edwards 270-SPO conventional pull stations.
The portables still have their Edwards 270-SPO conventional pull stations.
Line 40: Line 40:
==== Modules ====
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the south facing wall of the library and art room's sprinkler system's tamper and flow switches.
There are EST SIGA-CT1 addressable monitor modules supervising the south facing wall of the library and art room's sprinkler system's tamper and flow switches.
 
==Former System Specifications (1991-2015)==
== Former System Specifications (1991-2015) ==
 
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
! System Specifications
!System Specifications
|-
|-
|  
|
|-
|-
| FACP: Edwards Custom 6500 <br />FACP Location: Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br />Year Installed: 1991 <br /> Year Decomissioned: 2015
|FACP: Edwards Custom 6500 <br />FACP Location: Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br />Year Installed: 1991 <br /> Year Decomissioned: 2015
|}
|}
====FACP====
The building was protected by an Edwards Custom 6500 conventional fire alarm system. The panel was located in the electrical room. The system coding was continuous.
===== Annunciators =====
There was an Edwards annunciator at the entrance, model to be confirmed.
====Notification Appliances====
All notification appliances except for one are Edwards 439D-6AWC vibrating bells (6” gong), installed in 1985 and 1991 depending on the area; these are also in the portables.
Approximately 70% of bells are mounted on Edwards 403-5A-R strobe plates (15cd), which were added in 1996. The remaining bells are mostly installed remotely, most behind metal grills.
There is an Edwards 439D-10AWC vibrating bell (10” gong) located in a small hallway leading to the gymnasium.
For outdoor notification, there are Edwards 439D-6AWC bells located on each side.
All of these devices are still in use on the current system.
=== Initiating Devices ===
==== Pull Stations ====
All pull stations were Edwards 270-SPO conventional pull stations. The ones in the portables remained.
==== Automatic Detection Devices ====
There were Edwards 6250C conventional ionization smoke detectors throughout the school.
The portables had Edwards 281C conventional 135-degree fixed temperature/rate-of-rise heat detectors. These remained until being recalled in 2020.
There was also a sprinkler system covering the art room and south end of the library.
[[Category:Alberta]]
[[Category:Schools]]

Latest revision as of 19:06, 23 September 2024

System Specifications
FACP: Edwards EST3
FACP Location: Electrical Room
System Type: Single-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal?
Strobes Synchronized: No
Date of last known Upgrade: 2021
Year Opened: 1962


Cochrane High School is a large high school located at 529 4th Ave N, Cochrane, Alberta, Canada. The school opened in 1962, and expanded several times: 1966, 1970, 1972, 1985, with a second floor being added in 1991, and finally a modernization in 1996. Portables were installed in 1990 and 1992. The fire alarm system had an upgrade in 2015.

System Specifications (1991-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3 hybrid-addressable fire alarm system. The panel is located in an electrical room. The system runs EST’s Signature addressable protocol, and the system coding is likely temporal.

The panel replaced an Edwards Custom 6500 in 2015, and the system was upgraded to mostly addressable.

Annunciators[edit | edit source]

There is an Edwards EST 3-LCDANN LCD annunciator in the lobby, with an LCDXL1 display.

Notification Appliances[edit | edit source]

All notification appliances except for one are Edwards 439D-6AWC vibrating bells (6” gong), installed in 1991 or 1996 depending on the area; these are also in the portables.

Approximately 70% of bells are mounted on Edwards 403-5A-R strobe plates (15cd), which were added in 1996. The remaining bells are mostly installed remotely, most behind metal grills.

There is an Edwards 439D-10AWC vibrating bell (10” gong) located in a small hallway leading to the gymnasium.

For outdoor notification, there are Edwards 439D-6AWC bells located on each side.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations in the main building are EST SIGA-270 addressable single-action pull stations.

The portables still have their Edwards 270-SPO conventional pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA2-PS addressable photoelectric smoke detectors throughout the building.

There are a few Edwards SIGA-SD addressable photoelectric smoke detectors, installed as deficiency replacements. All smoke detectors are mounted on SIGA-SB bases.

There are also Edwards EC20RRU-3 rate-of-rise heat detectors in the portables, installed in 2020 replacing Edwards 281C heat detectors after being recalled.

The art room and south facing wall of the library are also protected by a sprinkler system, added in 1985.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the south facing wall of the library and art room's sprinkler system's tamper and flow switches.

Former System Specifications (1991-2015)[edit | edit source]

System Specifications
FACP: Edwards Custom 6500
FACP Location: Electrical Room
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Installed: 1991
Year Decomissioned: 2015

FACP[edit | edit source]

The building was protected by an Edwards Custom 6500 conventional fire alarm system. The panel was located in the electrical room. The system coding was continuous.

Annunciators[edit | edit source]

There was an Edwards annunciator at the entrance, model to be confirmed.

Notification Appliances[edit | edit source]

All notification appliances except for one are Edwards 439D-6AWC vibrating bells (6” gong), installed in 1985 and 1991 depending on the area; these are also in the portables.

Approximately 70% of bells are mounted on Edwards 403-5A-R strobe plates (15cd), which were added in 1996. The remaining bells are mostly installed remotely, most behind metal grills.

There is an Edwards 439D-10AWC vibrating bell (10” gong) located in a small hallway leading to the gymnasium.

For outdoor notification, there are Edwards 439D-6AWC bells located on each side.

All of these devices are still in use on the current system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Edwards 270-SPO conventional pull stations. The ones in the portables remained.

Automatic Detection Devices[edit | edit source]

There were Edwards 6250C conventional ionization smoke detectors throughout the school.

The portables had Edwards 281C conventional 135-degree fixed temperature/rate-of-rise heat detectors. These remained until being recalled in 2020.

There was also a sprinkler system covering the art room and south end of the library.