Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

HI Banff Alpine Centre: Difference between revisions

From FireAlarmPedia
(adding infobox)
 
(3 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Notifier NFS-320C <br /> FACP Location: Main Entrance Vestibule <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized <br />Date of last known Upgrade: 2017 <br />Year Opened: 1950s, 1986
| FACP: Notifier NFS-320C <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: 2017 <br />Year Opened: 1950s, 1986
|}
|}
'''HI Banff Alpine Centre''' is a hostel located at 801 Hidden Ridge Way, in Banff, Alberta, Canada. It consists of two buildings, the main building, built in the 1950s and renovated in 1986 as a hostel, and the Mary Belle Building, built in 1998. The main building's fire alarm system was upgraded in 2017, and the Mary Belle Building has the original fire alarm system.  
'''HI Banff Alpine Centre''' is a hostel located at 801 Hidden Ridge Way, in Banff, Alberta, Canada. It consists of two buildings, the main building, built in the 1950s and renovated in 1986 as a hostel, and the Mary Belle Building, built in 1998. The main building's fire alarm system was upgraded in 2017, and the Mary Belle Building has the original fire alarm system.  
Line 19: Line 19:
There are Notifier FSP-851 addressable photoelectric smoke detectors in some areas.
There are Notifier FSP-851 addressable photoelectric smoke detectors in some areas.


There are Notifier FST-851RA addressable thermal heat detectors in the kitchens and storage areas.
There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchens and storage areas.


All detectors are mounted on System Sensor B210LPA bases.
All detectors are mounted on System Sensor B210LPA bases.
==== EOLs ====
There are Notifier EOL-CR end of line resistor plates on all signal circuits.


== System Specifications (Main Building) (1986-2017) ==
== System Specifications (Main Building) (1986-2017) ==
Line 30: Line 33:
|  
|  
|-
|-
| FACP: Edwards 2280 <br /> FACP Location: Main Entrance Vestibule <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2015 <br />Year Installed: 1986 <br /> Year Decommissioned: 2017
| FACP: Edwards 2280 <br /> FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2015 <br />Year Installed: 1986 <br /> Year Decommissioned: 2017
|}
|}
==== FACP ====
==== FACP ====
The building was protected by an Edwards 2280 conventional fire alarm system. The panel was located in the main entrance vestibule. The system coding was continuous.
The building was protected by an Edwards 2280 conventional fire alarm system. The panel was located in the main entrance vestibule. The system coding was continuous.
==== Notification Appliances ====
==== Notification Appliances ====
Most notification appliances were Edwards "Durabel" 6100D vibrating bells (6" gong).
Most notification appliances were Edwards "Durabel" 6100D vibrating bells (6" gong).


There was an Edwards 439D-6AWC vibrating bell (6" gong) on EST 403-5A-R strobe plate (15cd) in the Storm Cellar, installed in 2015.
There was an Edwards 439D-6AWC vibrating bell (6" gong) on EST 403-5A-R strobe plate (15cd) in the Storm Cellar, installed in 2015.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
Most pull stations were Edwards 270-SPO conventional single-action pull stations.
Most pull stations were Edwards 270-SPO conventional single-action pull stations.
Line 48: Line 48:


There were two Pyrene 950-1050 conventional pull stations at the entrance and common eating area as deficiency replacements.
There were two Pyrene 950-1050 conventional pull stations at the entrance and common eating area as deficiency replacements.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There were System Sensor "i3" C2W-BA conventional photoelectric smoke detectors in some areas, installed in 2015 replacing older unknown ionization smoke detectors.
There were System Sensor "i3" C2W-BA conventional photoelectric smoke detectors in some areas, installed in 2015 replacing older unknown ionization smoke detectors.
Line 57: Line 56:


There was also an FDD CR135 135 degree fixed temperature/rate-of-rise heat detector in the Storm Cellar as a deficiency replacement.  
There was also an FDD CR135 135 degree fixed temperature/rate-of-rise heat detector in the Storm Cellar as a deficiency replacement.  
== System Specifications (Mary Belle Building) (1998-present) ==
== System Specifications (Mary Belle Building) (1998-present) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 65: Line 63:
|  
|  
|-
|-
| FACP: Edwards EST2 <br /> FACP Location: Main Entrance Vestibule <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br> Strobes Synchronized <br />Date of last known Upgrade: 2016 <br />Year Opened: 1998
| FACP: Edwards EST2 <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No<br />Date of last known Upgrade: 2016 <br />Year Opened: 1998
|}
|}
==== FACP ====
==== FACP ====
The building is protected by an Edwards EST2 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is continuous.
The building is protected by an Edwards EST2 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is continuous.
==== Notification Appliances ====
==== Notification Appliances ====
All common area notification appliances but one are Edwards 439D-6AWC vibrating bells (6" gong) mounted on EST 403-5A-R strobe plates (15cd).
All common area audible notification appliances but one are Edwards 439D-6AWC vibrating bells (6" gong). Most are mounted on EST 403-5A-R strobe plates (15cd).


There is a Wheelock RSSP-24MCW strobe plate (red, set to 15cd) in the lobby as a deficiency replacement in 2016; the bell remains intact.
There is a Wheelock RSSP-24MCW strobe plate (red, set to 15cd) in the lobby as a deficiency replacement in 2016; the bell remains intact.


The guest rooms have EST 692-5A-HSR mini-horn/strobes (red, wall-mount, 15cd).
The guest rooms have EST 692-5A-HSR mini-horn/strobes (red, wall-mount, 15cd).
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All pull stations are EST SIGA-270 addressable single-action pull stations.
All pull stations are EST SIGA-270 addressable single-action pull stations.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There are EST SIGA-PS addressable photoelectric smoke detectors in some areas.  
There are EST SIGA-PS addressable photoelectric smoke detectors in some areas.  


The rooms and kitchen have EST SIGA-HRS addressable rate-of-rise/fixed temperature heat detectors.
The rooms and kitchen have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.


All detectors are mounted on SIGA-SB bases.
All detectors are mounted on SIGA-SB bases.
==== EOLs ====
There are Edwards EOL-P1 end of line resistor plates on all Class-B signal circuits.
[[Category:Alberta]]
[[Category:Hostels]]

Latest revision as of 13:39, 29 September 2024

System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2017
Year Opened: 1950s, 1986

HI Banff Alpine Centre is a hostel located at 801 Hidden Ridge Way, in Banff, Alberta, Canada. It consists of two buildings, the main building, built in the 1950s and renovated in 1986 as a hostel, and the Mary Belle Building, built in 1998. The main building's fire alarm system was upgraded in 2017, and the Mary Belle Building has the original fire alarm system.

System Specifications (Main Building) (2017-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851 addressable photoelectric smoke detectors in some areas.

There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchens and storage areas.

All detectors are mounted on System Sensor B210LPA bases.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all signal circuits.

System Specifications (Main Building) (1986-2017)[edit | edit source]

System Specifications
FACP: Edwards 2280
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2015
Year Installed: 1986
Year Decommissioned: 2017

FACP[edit | edit source]

The building was protected by an Edwards 2280 conventional fire alarm system. The panel was located in the main entrance vestibule. The system coding was continuous.

Notification Appliances[edit | edit source]

Most notification appliances were Edwards "Durabel" 6100D vibrating bells (6" gong).

There was an Edwards 439D-6AWC vibrating bell (6" gong) on EST 403-5A-R strobe plate (15cd) in the Storm Cellar, installed in 2015.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

Most pull stations were Edwards 270-SPO conventional single-action pull stations.

There was an Edwards 274-111 conventional pull station in the Storm Cellar.

There were two Pyrene 950-1050 conventional pull stations at the entrance and common eating area as deficiency replacements.

Automatic Detection Devices[edit | edit source]

There were System Sensor "i3" C2W-BA conventional photoelectric smoke detectors in some areas, installed in 2015 replacing older unknown ionization smoke detectors.

There were Edwards 282A conventional rate-of-rise/197 degree fixed-temperature heat detectors in the kitchen and other areas.

There was a System Sensor 5601A conventional rate-of-rise/135 degree fixed-temperature heat detector in the Cougar Pete's as a deficiency replacement.

There was also an FDD CR135 135 degree fixed temperature/rate-of-rise heat detector in the Storm Cellar as a deficiency replacement.

System Specifications (Mary Belle Building) (1998-present)[edit | edit source]

System Specifications
FACP: Edwards EST2
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2016
Year Opened: 1998

FACP[edit | edit source]

The building is protected by an Edwards EST2 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is continuous.

Notification Appliances[edit | edit source]

All common area audible notification appliances but one are Edwards 439D-6AWC vibrating bells (6" gong). Most are mounted on EST 403-5A-R strobe plates (15cd).

There is a Wheelock RSSP-24MCW strobe plate (red, set to 15cd) in the lobby as a deficiency replacement in 2016; the bell remains intact.

The guest rooms have EST 692-5A-HSR mini-horn/strobes (red, wall-mount, 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS addressable photoelectric smoke detectors in some areas.

The rooms and kitchen have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.

All detectors are mounted on SIGA-SB bases.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all Class-B signal circuits.