David Cameron Elementary: Difference between revisions

From FireAlarmPedia
(System is undergoing replacement)
No edit summary
 
(6 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|
|
|-
|-
|FACP: EST QuickStart QS4 <br />FACP Location: Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2021 <br />Year Opened: 1972, 1995
|FACP: Notifier NFS2-3030C<br />FACP Location: Electrical Room <br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: Yes, System Sensor<br />Date of last known Upgrade: 2024<br />Year Opened: 1972, 1995
|}
'''David Cameron Elementary''' is an elementary school located at 675 Meaford Ave, Victoria, BC. It is part of the Sooke School District. It was originally built in 1972, before being rebuilt in 1995 except for the gymnasium. The fire alarm system was recently upgraded. The school is currently looking to demolish the portables.
== System Specifications (2024-present) ==
==== FACP ====
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
==== Annunciators ====
There is a Notifier LCD2-80 LCD annunciator paired with an ACM-24AT LED annunciator in the lobby.
==== Notification Appliances ====
All notification appliances except for one are from System Sensor's "L-Series" line of products.
 
Most notification appliances are System Sensor P2RLA horn/strobes (red, wall-mount, set to 110cd/electromechanical). There is one per classroom, and one in the gymnasium. These are installed in the bells' spaces except for the gymnasium.
 
There are System Sensor SRLA remote strobes (red, wall-mount, set to 110cd) in the gymnasium, with one per classroom.
 
The bathrooms have System Sensor SCWLA remote strobes (white, ceiling-mount, set to 110cd).
 
For exterior notification, there is a System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobe (red, wall-mount, set to 60cd), fitted with a LENS-B (blue) lens for zone annunciation.
=== Initiating Devices ===
==== Pull Stations ====
All pull stations are Notifier N-MPS-SA addressable single-action pull stations. Most are fitted with MPS-LP dual-action conversion levers.
==== Automatic Detection Devices ====
There are Notifier FSP-951A addressable photoelectric smoke detectors throughout.
 
Some areas have Notifier FST-951RA addressable thermal heat detectors.
 
All detectors are mounted on System Sensor B300A-6 bases.
 
There are Notifier DNRA addressable photoelectric duct smoke detectors on the air handling units, fitted with FSP-951A addressable photoelectric heads.
==== Modules ====
There are Notifier ISO-6A isolator modules on the SLC.
 
==== EOLs ====
There are Notifier EOL-CR end of line resistor plates on all signal circuits.
 
==Former System Specifications (1995-2024)==
{| style="float:right;border:2px solid black"
|-
! Former System Specifications
|-
|
|-
| FACP: EST QuickStart QS4 <br />FACP Location: Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2012 <br/> Year Installed: 1995 <br />Year Decommissioned: 2024
|}
|}
'''David Cameron Elementary''' is an elementary school located at 675 Meaford Ave, Victoria, BC. It is part of the Sooke School District. It was originally built in 1972, before being rebuilt in 1995 except for the gymnasium. The fire alarm system is mostly original from the rebuild. The school is currently looking to expand the portables, and the system is currently being replaced
==System Specifications (1995-present)==
====FACP====
====FACP====
The building is protected by an EST QuickStart QS4 conventional fire alarm system. The panel is located in the electrical room, and replaced an EST ESA2000; the ESA2000 panel remains, but is decommissioned. The system coding is continuous.
The building was protected by an EST QuickStart QS4 conventional fire alarm system. The panel was located in the electrical room. The system coding was continuous.
 
This panel replaced an EST ESA2000 around 2012. The cabinet remains, but is decommissioned.
=====Boosters=====
=====Boosters=====
There are three Edwards EBPS6A 6.5A remote booster power supplies. One is in the ESA2000 cabinet, the other two are next to the QS4.
There were three Edwards EBPS6A 6.5A remote booster power supplies. One was in the ESA2000 cabinet, the other two were next to the QS4.
=====Annunciators=====
=====Annunciators=====
There is an Edwards EST-SRA4 remote LCD annunciator in the lobby.
There was an Edwards EST-SRA4 remote LCD annunciator in the lobby.
====Notification Appliances====
====Notification Appliances====
=====Main Building=====
=====Main Building=====
Most notification appliances are Edwards 439D-10AWC vibrating bells (10” gong) with EST 202-8A-001 remote strobes (red, wall-mount, 110cd) next to them. The mentioned bells are also installed remotely in one hallway (with a 202-8A-001 in between), in the electrical room and air handling room.  
Most notification appliances were Edwards 439D-10AWC vibrating bells (10” gong) with EST 202-8A-001 remote strobes (red, wall-mount, 110cd) next to them. The mentioned bells were also installed remotely in one hallway (with a 202-8A-001 in between), in the electrical room and air handling room.  


There are some Edwards MB10-24 motor bells (10” gong) installed as deficiency replacements.  
The library contained one Edwards 439D-10AWC vibrating bell (10” gong) and four EST 202-8A-001 remote strobes (red, wall-mount, 110cd).  


Each classroom and washroom contains an EST 202-8A-001 remote strobe, as the school was built for hard-of-hearing students.  
There were some Edwards MB10-24 motor bells (10” gong) installed as deficiency replacements.  


There are some EST “Integrity” 202-8A-T remote strobes (red, wall-mount, 110cd) installed as deficiency replacements.
Each classroom and washroom contained an EST 202-8A-001 remote strobe, as the school was built for hard-of-hearing students.  
=====Library=====
 
The library contains one Edwards 439D-10AWC vibrating bell (10” gong) and four EST 202-8A-001 remote strobes (red, wall-mount, 110cd)
There were some EST “Integrity” 202-8A-T remote strobes (red, wall-mount, 110cd) installed as deficiency replacements.
=====Portables=====
=====Portables=====
Portable 1 has a Simplex 2901-9724 motor bell (10” gong), and Portable 2 has an Edwards MB10-24 motor bell (10” gong).
Portable 1 had a Simplex 2901-9724 motor bell (10” gong), and Portable 2 had an Edwards MB10-24 motor bell (10” gong).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations in the main building are Edwards 270-SPOE conventional pull stations. The portables contain newer Edwards 270-SPO pull stations.
All pull stations in the main building were Edwards 270-SPOE conventional pull stations.  
 
The portables contained newer Edwards 270-SPO pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Edwards 6250C conventional ionization smoke detectors located throughout. There are also Edwards 281C rate-of-rise/fixed heat detectors in some areas.  
There were Edwards 6250C conventional ionization smoke detectors located throughout.  
 
There were also Edwards 281C rate-of-rise/fixed heat detectors in some areas.  


The portables contain System Sensor 5601A rate-of-rise/fixed heat detectors, one is also installed in a storage room in the main building as a deficiency replacement in 2021.  
The portables contained System Sensor 5601A rate-of-rise/fixed heat detectors, one was also installed in a storage room in the main building as a deficiency replacement in 2021.  


The air handling units have Edwards 6265B-001 duct detector housings with 6264B ionization smoke detector heads in them; these are connected to 6262B-001 keyswitch test stations.  
The air handling units had Edwards 6265B-001 duct detector housings with 6264B ionization smoke detector heads in them; these were connected to 6262B-001 keyswitch test stations.  
==Bonus Information==
==Bonus Information==
There is a System Sensor “L-Series” P2RLA horn/strobe in the building, but it is not hooked up to the fire alarm system.
There is a System Sensor “L-Series” P2RLA horn/strobe in the building, but it is not hooked up to the fire alarm system.
[[Category:British Columbia]]
[[Category:Schools]]

Latest revision as of 16:35, 24 September 2024

System Specifications
FACP: Notifier NFS2-3030C
FACP Location: Electrical Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2024
Year Opened: 1972, 1995

David Cameron Elementary is an elementary school located at 675 Meaford Ave, Victoria, BC. It is part of the Sooke School District. It was originally built in 1972, before being rebuilt in 1995 except for the gymnasium. The fire alarm system was recently upgraded. The school is currently looking to demolish the portables.

System Specifications (2024-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the electrical room. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Notifier LCD2-80 LCD annunciator paired with an ACM-24AT LED annunciator in the lobby.

Notification Appliances[edit | edit source]

All notification appliances except for one are from System Sensor's "L-Series" line of products.

Most notification appliances are System Sensor P2RLA horn/strobes (red, wall-mount, set to 110cd/electromechanical). There is one per classroom, and one in the gymnasium. These are installed in the bells' spaces except for the gymnasium.

There are System Sensor SRLA remote strobes (red, wall-mount, set to 110cd) in the gymnasium, with one per classroom.

The bathrooms have System Sensor SCWLA remote strobes (white, ceiling-mount, set to 110cd).

For exterior notification, there is a System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobe (red, wall-mount, set to 60cd), fitted with a LENS-B (blue) lens for zone annunciation.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier N-MPS-SA addressable single-action pull stations. Most are fitted with MPS-LP dual-action conversion levers.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-951A addressable photoelectric smoke detectors throughout.

Some areas have Notifier FST-951RA addressable thermal heat detectors.

All detectors are mounted on System Sensor B300A-6 bases.

There are Notifier DNRA addressable photoelectric duct smoke detectors on the air handling units, fitted with FSP-951A addressable photoelectric heads.

Modules[edit | edit source]

There are Notifier ISO-6A isolator modules on the SLC.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all signal circuits.

Former System Specifications (1995-2024)[edit | edit source]

Former System Specifications
FACP: EST QuickStart QS4
FACP Location: Electrical Room
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2012
Year Installed: 1995
Year Decommissioned: 2024

FACP[edit | edit source]

The building was protected by an EST QuickStart QS4 conventional fire alarm system. The panel was located in the electrical room. The system coding was continuous.

This panel replaced an EST ESA2000 around 2012. The cabinet remains, but is decommissioned.

Boosters[edit | edit source]

There were three Edwards EBPS6A 6.5A remote booster power supplies. One was in the ESA2000 cabinet, the other two were next to the QS4.

Annunciators[edit | edit source]

There was an Edwards EST-SRA4 remote LCD annunciator in the lobby.

Notification Appliances[edit | edit source]

Main Building[edit | edit source]

Most notification appliances were Edwards 439D-10AWC vibrating bells (10” gong) with EST 202-8A-001 remote strobes (red, wall-mount, 110cd) next to them. The mentioned bells were also installed remotely in one hallway (with a 202-8A-001 in between), in the electrical room and air handling room.

The library contained one Edwards 439D-10AWC vibrating bell (10” gong) and four EST 202-8A-001 remote strobes (red, wall-mount, 110cd).

There were some Edwards MB10-24 motor bells (10” gong) installed as deficiency replacements.

Each classroom and washroom contained an EST 202-8A-001 remote strobe, as the school was built for hard-of-hearing students.

There were some EST “Integrity” 202-8A-T remote strobes (red, wall-mount, 110cd) installed as deficiency replacements.

Portables[edit | edit source]

Portable 1 had a Simplex 2901-9724 motor bell (10” gong), and Portable 2 had an Edwards MB10-24 motor bell (10” gong).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations in the main building were Edwards 270-SPOE conventional pull stations.

The portables contained newer Edwards 270-SPO pull stations.

Automatic Detection Devices[edit | edit source]

There were Edwards 6250C conventional ionization smoke detectors located throughout.

There were also Edwards 281C rate-of-rise/fixed heat detectors in some areas.

The portables contained System Sensor 5601A rate-of-rise/fixed heat detectors, one was also installed in a storage room in the main building as a deficiency replacement in 2021.

The air handling units had Edwards 6265B-001 duct detector housings with 6264B ionization smoke detector heads in them; these were connected to 6262B-001 keyswitch test stations.

Bonus Information[edit | edit source]

There is a System Sensor “L-Series” P2RLA horn/strobe in the building, but it is not hooked up to the fire alarm system.