Line 5: Line 5:
|  
|  
|-
|-
| FACP: Simplex 4100ES <br />FACP Location: Unknown <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 25VRMS (audible) <br> 24VDC (visual) <br />System Coding: Slow Whoop + Custom Message <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: N/A <br />Year Opened: 2012
| FACP: Simplex 4100ES <br />FACP Location: Unknown <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 25VRMS (audible) <br>24VDC (visual) <br />System Coding: Slow Whoop + Custom Message <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: N/A <br />Year Opened: 2012
|}
|}
 
The '''Northern Alberta Institute of Technology''' (NAIT) is a technical college located in Edmonton, Alberta, Canada. This page will cover the East Parkade. It was built in 2012, and the fire alarm system is original.
The '''Northern Alberta Institute of Technology''' (NAIT) is a technical college located in Edmonton, Alberta, Canada. This page will cover the East Parkade. It was built in 2012, and the fire alarm system is original.
 
== System Specifications (2012-present) ==
== System Specifications (2012-present) ==
==== FACP ====
==== FACP ====
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel location is unknown. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice-evacuation. The evacuation signal is slow whoop and a custom voice message.
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel location is unknown. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice-evacuation. The evacuation signal is slow whoop and a custom voice message.
==== Notification Appliances ====
==== Notification Appliances ====
All notification appliances are System Sensor “SpectrAlert Advance” SPRKA weatherproof speakers (red, wall-mount), with Simplex “TrueAlert” 4906-9105 weatherproof strobes (red, wall-mount, set to 60cd) underneath them.
All notification appliances are System Sensor “SpectrAlert Advance” SPRKA weatherproof speakers (red, wall-mount), with Simplex “TrueAlert” 4906-9105 weatherproof strobes (red, wall-mount, set to 60cd) underneath them.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout, mounted on 4098-9792 bases.
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout, mounted on 4098-9792 bases.


==== Modules ====
==== Modules ====
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
==== EOLs ====
There are Simplex 2081-9040C end of line resistor plates on all signal circuits.


There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
[[Category:Edmonton]]
[[Category:Post-Secondary]]

Latest revision as of 20:30, 13 October 2024

System Specifications
FACP: Simplex 4100ES
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 25VRMS (audible)
24VDC (visual)
System Coding: Slow Whoop + Custom Message
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: N/A
Year Opened: 2012

The Northern Alberta Institute of Technology (NAIT) is a technical college located in Edmonton, Alberta, Canada. This page will cover the East Parkade. It was built in 2012, and the fire alarm system is original.

System Specifications (2012-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4100ES addressable fire alarm system. The panel location is unknown. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice-evacuation. The evacuation signal is slow whoop and a custom voice message.

Notification Appliances[edit | edit source]

All notification appliances are System Sensor “SpectrAlert Advance” SPRKA weatherproof speakers (red, wall-mount), with Simplex “TrueAlert” 4906-9105 weatherproof strobes (red, wall-mount, set to 60cd) underneath them.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout, mounted on 4098-9792 bases.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all signal circuits.