Hilton Garden Inn Calgary Airport: Difference between revisions

From FireAlarmPedia
No edit summary
(Eduardo2)
 
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST2 <br />FACP Location: Data Room behind Front Desk <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal (Common Areas) <br>Continuous (Guest Rooms) <br>Strobes Synchronized: Yes, Per-NAC <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
| FACP: Edwards EST2 <br />FACP Location: Data Room behind Front Desk <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal (Common Areas) <br>Continuous (Guest Rooms) <br>Strobes Synchronized: Yes, Per-NAC <br />Date of last known Upgrade: N/A <br />Year Opened: 1999
|}
|}
'''Hilton Garden Inn''' is a chain of midrange hotels owned by Hilton. The chain is headquartered in Mclean, VA, and has locations worldwide. This particular hotel is located at 2335 Pegasus Road NE, in Calgary, AB. The hotel opened in 1999, and the fire alarm system is original, with deficiency replacements installed as they occur.
'''Hilton Garden Inn''' is a chain of midrange hotels owned by Hilton. The chain is headquartered in Mclean, VA, and has locations worldwide. This particular hotel is located at 2335 Pegasus Road NE, in Calgary, AB. The hotel opened in 1999, and the fire alarm system is original, with deficiency replacements installed as they occur.
Line 24: Line 24:
====Modules====
====Modules====
There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br>There is an EST SIGA-CT1 addressable monitor module supervising the kitchen suppression system. <br>There are EST SIGA-CR addressable relay modules for air handling unit shutdown.
There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br>There is an EST SIGA-CT1 addressable monitor module supervising the kitchen suppression system. <br>There are EST SIGA-CR addressable relay modules for air handling unit shutdown.
==== EOLs ====
There are Edwards EOL-P1 end of line resistor plates on the kitchen suppression, sprinkler and signal circuits.
[[Category:Calgary]]
[[Category:Calgary]]
[[Category:Hotels]]
[[Category:Hotels]]

Latest revision as of 10:48, 30 September 2024

System Specifications
FACP: Edwards EST2
FACP Location: Data Room behind Front Desk
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal (Common Areas)
Continuous (Guest Rooms)
Strobes Synchronized: Yes, Per-NAC
Date of last known Upgrade: N/A
Year Opened: 1999

Hilton Garden Inn is a chain of midrange hotels owned by Hilton. The chain is headquartered in Mclean, VA, and has locations worldwide. This particular hotel is located at 2335 Pegasus Road NE, in Calgary, AB. The hotel opened in 1999, and the fire alarm system is original, with deficiency replacements installed as they occur.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST2 addressable fire alarm system. The panel is located in a data room behind the front desk. The system runs Edwards’ Signature addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is an Edwards EST2-LSRA-C annunciator in the main entrance vestibule.

Boosters[edit | edit source]

There are three Edwards APSBB booster power supplies in the main panel.

Notification Appliances[edit | edit source]

All common areas have Edwards “Integrity” 757-5A-T horn/strobes (red, wall-mount, 15cd).
All guest rooms have Edwards 692-5A-001 mini horn/strobes (red, wall-mount, 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PHS addressable photoelectric smoke/135°F fixed-temperature heat detectors throughout all corridors.
There are EST SIGA-HFS addressable 135°F fixed-temperature heat detectors in the breakfast area, kitchen and elevator shafts.
There is an Edwards SIGA-OSD addressable optical smoke detector in the elevator machine room.
There are EST SIGA-DH duct detector housings with EST SIGA-PS addressable photoelectric smoke detector heads on all air handling units.
All detectors are mounted on EST SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There is an EST SIGA-CT1 addressable monitor module supervising the kitchen suppression system.
There are EST SIGA-CR addressable relay modules for air handling unit shutdown.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on the kitchen suppression, sprinkler and signal circuits.