Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Olympic Heights School: Difference between revisions

From FireAlarmPedia
No edit summary
No edit summary
 
(One intermediate revision by the same user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Notifier NFS-320C <br /> FACP Location: Main Entrance <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, SS <br />Date of last known Upgrade: 2010s <br />Year Opened: 1991
| FACP: Notifier NFS-320C <br /> FACP Location: Main Entrance <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, SS <br />Date of last known Upgrade: 2010s <br />Year Opened: 1991
|}
|}
'''Olympic Heights School''' is an elementary school located at 875 Strathcona Drive Southwest, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. The school opened in 1991, and the fire alarm system was upgraded in about 2014.
'''Olympic Heights School''' is an elementary school located at 875 Strathcona Drive Southwest, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. The school opened in 1991, and the fire alarm system was upgraded in about 2014.
Line 18: Line 18:
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B210LPA low-profile bases.
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B210LPA low-profile bases.
==== EOLs ====
There are Notifier EOL-CR end of line resistor plates on all signal circuits.
==System Specifications (1996-2014)==
==System Specifications (1996-2014)==
Please note that this section is incomplete. All information regarding this system was found in a RECAPP Facility report.
Please note that this section is incomplete. All information regarding this system was found in a RECAPP Facility report.

Latest revision as of 18:34, 9 October 2024

System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SS
Date of last known Upgrade: 2010s
Year Opened: 1991

Olympic Heights School is an elementary school located at 875 Strathcona Drive Southwest, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. The school opened in 1991, and the fire alarm system was upgraded in about 2014.

System Specifications (2014-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located at the main entrance. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All areas except washrooms have System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). The washrooms have System Sensor SRA remote strobes (red, wall-mount, set to 15cd). For outdoor notification, there is a System Sensor P2RKA weatherproof horn/strobe (red, wall-mount) outside the main entrance.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B210LPA low-profile bases.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all signal circuits.

System Specifications (1996-2014)[edit | edit source]

Please note that this section is incomplete. All information regarding this system was found in a RECAPP Facility report.

FACP[edit | edit source]

The building was protected by a Simplex fire alarm system. No additional information is known.

Notification Appliances[edit | edit source]

All notification appliances were Simplex 2901-9720 motor bells (6” gong).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Simplex, model unknown.

Automatic Detection Devices[edit | edit source]

Not known.