| FACP: Edwards EST3 <br />FACP Location: Fire Alarm Panel Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br />System Coding: 20BPM (Alert) <br> Temporal (Alarm) <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: 2020s <br />Year Opened: 1982 | | FACP: Edwards EST3 <br />FACP Location: Fire Alarm Panel Room <br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br />System Coding: 20BPM (Alert) <br> Temporal (Alarm) <br>Strobes Synchronized: Yes, Genesis <br />Date of last known Upgrade: 2020s <br />Year Opened: 1982 | ||
|} | |} | ||
The '''Whitehorn Multi Services Centre''' is a City of Calgary building located at 3705 35 Street Northeast, in Calgary, Alberta, Canada. The building was built in 1982 as the head office for Nortel, and was taken over by the city in the 2000s. The fire alarm system was fully upgraded in the early 2010s. | The '''Whitehorn Multi Services Centre''' is a City of Calgary building located at 3705 35 Street Northeast, in Calgary, Alberta, Canada. The building was built in 1982 as the head office for Nortel, and was taken over by the city in the 2000s. The fire alarm system was fully upgraded in the early 2010s. | ||
Line 26: | Line 26: | ||
====Modules==== | ====Modules==== | ||
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
==== EOLs ==== | |||
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits. | |||
[[Category:Calgary]] | [[Category:Calgary]] | ||
[[Category:Government Services]] | [[Category:Government Services]] |
Latest revision as of 20:34, 14 October 2024
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Fire Alarm Panel Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2020s Year Opened: 1982 |
The Whitehorn Multi Services Centre is a City of Calgary building located at 3705 35 Street Northeast, in Calgary, Alberta, Canada. The building was built in 1982 as the head office for Nortel, and was taken over by the city in the 2000s. The fire alarm system was fully upgraded in the early 2010s.
System Specifications (2010s-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by an Edwards EST3 addressable fire alarm system. The system is networked, and the main FACP is located in the fire alarm panel room. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is a temporal tone; both signals have voice messages.
Boosters[edit | edit source]
There is an Edwards BPS10A booster power supply in a data closet.
Notification Appliances[edit | edit source]
Most areas have a mix of Edwards “Genesis” G4-S7 remote speakers (white, wall-mount, 70V) and Edwards GC-S7 remote speakers (white, ceiling-mount, 70V).
Renovated areas have a mix of Edwards G4SVWF speaker/strobes (white, wall-mount, set to 15cd) and Edwards GCSVWF speaker/strobes (white, ceiling-mount, set to 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are EST SIGA-PS addressable photoelectric smoke detectors in some areas. Other areas have EST SIGA-HFS addressable fixed-temperature and EST SIGA-HRS addressable fixed/rate-of-rise heat detectors. All detectors are mounted on EST SIGA-SB bases.
Modules[edit | edit source]
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.