More actions
Twentytwo22 (talk | contribs) mNo edit summary |
(Strobs) |
||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Edwards EST3 <br />FACP Location: Basement Electrical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (Alert) <br> | | FACP: Edwards EST3 <br />FACP Location: Basement Electrical Room <br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (Alert) <br>Continuous (Alarm) <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2010 <br />Year Opened: 1978 | ||
|} | |} | ||
'''Carewest Dr. Vernon Fanning Centre''' is an adult care facility located at 722 16 Avenue NE, in Calgary, Alberta, Canada. The facility is owned and operated by Alberta Health Services. The facility opened in 1978, and the fire alarm system was upgraded in 2010. | '''Carewest Dr. Vernon Fanning Centre''' is an adult care facility located at 722 16 Avenue NE, in Calgary, Alberta, Canada. The facility is owned and operated by Alberta Health Services. The facility opened in 1978, and the fire alarm system was upgraded in 2010. | ||
==System Specifications (2010-present)== | ==System Specifications (2010-present)== | ||
====FACP==== | ====FACP==== | ||
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the basement electrical room. The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the evacuation signal | The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the basement electrical room. The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the evacuation signal is continuous. | ||
=====Annunciators===== | =====Annunciators===== | ||
There is an Edwards EST3-LCDANN annunciator with an LCDXL1 display in the main entrance vestibule. <br>There are Edwards EST3-3ANN annunciator cabinets with EST3-24R annunciation cards at all nurse’s stations. | There is an Edwards EST3-LCDANN annunciator with an LCDXL1 display in the main entrance vestibule. <br>There are Edwards EST3-3ANN annunciator cabinets with EST3-24R annunciation cards at all nurse’s stations. | ||
Line 29: | Line 29: | ||
| | | | ||
|- | |- | ||
| FACP: Edwards 8500 <br />FACP Location: Basement Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (alert) <br> 120BPM March Time (alarm) <br />Date of last known Upgrade: 1991 <br />Year Installed: 1978 <br /> Year Decommissioned: 2010 | | FACP: Edwards 8500 <br />FACP Location: Basement Electrical Room <br />System Type: Two-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (alert) <br> 120BPM March Time (alarm) <br />Date of last known Upgrade: 1991 <br />Year Installed: 1978 <br /> Year Decommissioned: 2010 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== |
Latest revision as of 20:02, 19 September 2024
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Basement Electrical Room System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Continuous (Alarm) Strobes Synchronized: Yes, EST Date of last known Upgrade: 2010 Year Opened: 1978 |
Carewest Dr. Vernon Fanning Centre is an adult care facility located at 722 16 Avenue NE, in Calgary, Alberta, Canada. The facility is owned and operated by Alberta Health Services. The facility opened in 1978, and the fire alarm system was upgraded in 2010.
System Specifications (2010-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by an Edwards EST3 addressable fire alarm system. The panel is located in the basement electrical room. The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert coding is 20BPM, and the evacuation signal is continuous.
Annunciators[edit | edit source]
There is an Edwards EST3-LCDANN annunciator with an LCDXL1 display in the main entrance vestibule.
There are Edwards EST3-3ANN annunciator cabinets with EST3-24R annunciation cards at all nurse’s stations.
Notification Appliances[edit | edit source]
Most notification appliances are Edwards 439D-10AWC vibrating bells (10” gong).
There are Edwards “Integrity” 202-7A-T remote strobes (red, wall-mount, 15/75cd) next to most bells.
The electrical room has an Edwards MB10-24 motor bell (10” gong) with an Edwards “Genesis” G1R-VM remote strobe (red, wall-mount, no marking, set to 15cd) mounted next to it.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building.
Some areas have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on EST SIGA-SB bases.
Modules[edit | edit source]
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
Former System Specifications (1978-2010) (Assumed Devices)[edit | edit source]
System Specifications |
---|
FACP: Edwards 8500 FACP Location: Basement Electrical Room System Type: Two-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (alert) 120BPM March Time (alarm) Date of last known Upgrade: 1991 Year Installed: 1978 Year Decommissioned: 2010 |
FACP[edit | edit source]
The building was protected by an Edwards 8500 conventional fire alarm system. The panel was located in the basement electrical room. The system was configured for two-stage operation. The alert coding was 20BPM, followed by 120BPM march time in general alarm.
Annunciators[edit | edit source]
There were Edwards annunciators at all nurse’s stations and the main entrance vestibule, model to be confirmed.
Notification Appliances[edit | edit source]
All notification appliances in the original portion were Edwards “Adaptabel” 333D single-stroke bells (10” gong).
The 1991 renovation had Edwards 439D-10AWC vibrating bells (10” gong).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Edwards 270-GAO conventional two-stage pull stations.
Automatic Detection Devices[edit | edit source]
There were Edwards 282A 197 degree fixed-temperature/rate-of-rise heat detectors in the original portion.
The 1991 portion had Edwards 6250C conventional ionization smoke detectors.