The building is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located next to the main entrance. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
The building is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located next to the main entrance. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
====Notification Appliances====
====Notification Appliances====
====== Common Areas ======
====== Common Areas ======
Line 23: Line 23:
====Modules====
====Modules====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Hotels]]
[[Category:Hotels]]
[[Category:Calgary]]
[[Category:Calgary]]

Revision as of 21:50, 13 August 2024

System Specifications
FACP: EST QuickStart QS1
FACP Location: Next to Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage:24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, EST Self-Sync
Date of last known Upgrade: N/A
Year Opened: 2006

Sandman is a Canadian hotel chain headquartered in Vancouver, British Columbia. This particular hotel is located at 125 Bowridge Dr NW, in Calgary, Alberta, Canada. The hotel opened in 2006, and the fire alarm system is original. This page also covers the attached Denny's restaurant.

System Specifications (2006-present)

FACP

The building is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located next to the main entrance. The system runs EST’s Signature addressable protocol, and the system coding is temporal.

Notification Appliances

Common Areas

There are EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd) throughout all common areas.

Guest Rooms

All guest rooms have Edwards 683-1C silenceable mini-horns (white, wall-mount) and EST "Genesis" G1-VM remote strobes (white, wall-mount, no lettering, set to 15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the hotel's common areas, mounted on EST SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs