Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

Edmonton Animal Control & Care Centre: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: N/A <br />Year Opened: 2010 |} The Animal Control & Care Centre is a municipal building owned by the city of E...")
 
No edit summary
 
Line 28: Line 28:
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====


There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B710LPA bases.
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA bases.


==== Modules ====
==== Modules ====

Latest revision as of 22:13, 18 March 2025

System Specifications
FACP: Notifier NFS-320C
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: N/A
Year Opened: 2010

The Animal Control & Care Centre is a municipal building owned by the city of Edmonton for lost or stray animals. It is located at 13550 163 St NW, Edmonton, AB. It was built in 2010, and the fire alarm system is original.

System Specifications (2010-present)

FACP

The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

Most notification appliances are System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobes (red, wall-mount, set to 75cd).
Some areas have System Sensor P2RA horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices

Pull Stations

Most pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Some areas have Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA bases.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs

There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.