(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: N/A <br />Year Opened: 2010 |} The Animal Control & Care Centre is a municipal building owned by the city of E...") |
No edit summary |
||
| Line 28: | Line 28: | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on | There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA bases. | ||
==== Modules ==== | ==== Modules ==== | ||
Latest revision as of 22:13, 18 March 2025
| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2010 |
The Animal Control & Care Centre is a municipal building owned by the city of Edmonton for lost or stray animals. It is located at 13550 163 St NW, Edmonton, AB. It was built in 2010, and the fire alarm system is original.
System Specifications (2010-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
Most notification appliances are System Sensor "SpectrAlert Advance" P2RKA weatherproof horn/strobes (red, wall-mount, set to 75cd).
Some areas have System Sensor P2RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
Most pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
Some areas have Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA bases.
Modules
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.