Calgary Soccer Centre: Difference between revisions

From FireAlarmPedia
mNo edit summary
(Page fully remade, copied from Drive.)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Notifier NFS2-640C <br />System Type: Hybrid (Networked) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VD <br />Date of last known Upgrade: 2016 <br />Year Opened: 1990
| FACP: Notifier NFS2-640C <br /> FACP Location: Main Entrance <br />System Type: Hybrid-Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2016 <br />Year Opened: 1990
|}
|}


'''Calgary Soccer Centre''' is a fieldhouse located in the Foothills Industrial area of Southeast Calgary.  There are two buildings here.  One is the main building, built in 1990.  The other is the annex, built in 2016.  The annex’s system is entirely original, and the main building’s system is mostly original.
 
'''Calgary Soccer Centre''' is a fieldhouse located in the Foothills Industrial area of Southeast Calgary, Alberta, Canada.  There are two buildings here.  One is the main building, built in 1990.  The other is the annex, built in 2016.  The annex’s system is entirely original, and the main building’s system is mostly original.


==System Specifications (main building)==
==System Specifications (main building)==
====FACP====
====FACP====
The building is protected by a Notifier NFS2-640C addressable fire alarm system.  The panel is located at the main entrance, and was installed in 2016 when the annex openedThis panel is networked to the one in the annex.  When in alarm, the system does code 3.
The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system.  The panel is located in the main entrance vestibuleThe system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.


====Notification Appliances====
====Notification Appliances====
All notification appliances are the original Edwards 439D-10AWC vibrating bells (10” gong).
All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong).


===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
Most pull stations are Edwards 275-C111 conventional single-action pull stations, which are original. Some of these pull stations have failed, and were replaced with Edwards 270-SPO conventional single-action “teardrop” pull stations.
Most pull stations are Edwards 275-C111 conventional single-action pull stations. Some areas have Edwards 270-SPO conventional single-action pull stations as deficiency replacements.


====Automatic Detection Devices====
====Automatic Detection Devices====
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the facility.
The field areas have System Sensor BEAM1224 beam detectors.


==System Specifications (Annex)==
==System Specifications (Annex)==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Notifier NFS2-640C <br />System Type: Addressable (Networked) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: N/A <br />Year Opened: 2016
|}
====FACP====
====FACP====
The building is protected by a Notifier NFS2-640C addressable fire alarm system.  This panel is located at the main entrance, and is original to the building.  This panel is networked to the one in the main building. When in alarm, the system does code 3.
The building is protected by a Notifier NFS2-640C addressable fire alarm system.  This panel is located in the main entrance vestibule.  The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal..


====Notification Appliances====
====Notification Appliances====
All notification appliances are from System Sensor’s “SpectrAlert Advance” line of products.  The corridors and locker rooms have System Sensor P2RA horn/strobes (red, wall-mount) set on code 3, medium volume.  The fields have System Sensor PC2RA horn/strobes (red, ceiling-mount) set on code 3, high volume.
Most notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount).  The fields have System Sensor PC2RA horn/strobes (red, ceiling-mount).


===Initiating Devices===
===Initiating Devices===
Line 44: Line 37:


====Automatic Detection Devices====
====Automatic Detection Devices====
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the facility.
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the facility, mounted on System Sensor B210LPA low-profile bases.

Revision as of 10:28, 18 November 2022

System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Entrance
System Type: Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2016
Year Opened: 1990


Calgary Soccer Centre is a fieldhouse located in the Foothills Industrial area of Southeast Calgary, Alberta, Canada. There are two buildings here. One is the main building, built in 1990. The other is the annex, built in 2016. The annex’s system is entirely original, and the main building’s system is mostly original.

System Specifications (main building)

FACP

The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances

All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong).

Initiating Devices

Pull Stations

Most pull stations are Edwards 275-C111 conventional single-action pull stations. Some areas have Edwards 270-SPO conventional single-action pull stations as deficiency replacements.

Automatic Detection Devices

The field areas have System Sensor BEAM1224 beam detectors.

System Specifications (Annex)

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. This panel is located in the main entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal..

Notification Appliances

Most notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount). The fields have System Sensor PC2RA horn/strobes (red, ceiling-mount).

Initiating Devices

Pull Stations

All pull stations are Notifier N-MPS-SA addressable single-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the facility, mounted on System Sensor B210LPA low-profile bases.