More actions
(Page remade to fit modern format.) |
(You can press Ctrl+Enter to save your edit. Shut the fuck up, MediaWiki. Anyways, corrected the addressable protocol.) |
||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: EST3 | | FACP: EST3 | ||
FACP Location: Unknown<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) | FACP Location: Unknown<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) | ||
Line 13: | Line 13: | ||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The tower is protected by an Edwards EST3 addressable fire alarm system. | The tower is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs EST's Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
Most areas have EST "Genesis" G4-S7VM speaker/strobes (white, wall-mount, 70V, set to 15cd). The restrooms and possibly other areas have EST G1-VM remote strobes (white, wall-mount, no lettering, set to 15cd). | Most areas have EST "Genesis" G4-S7VM speaker/strobes (white, wall-mount, 70V, set to 15cd). The restrooms and possibly other areas have EST G1-VM remote strobes (white, wall-mount, no lettering, set to 15cd). |
Revision as of 11:51, 10 January 2023
System Specifications |
---|
FACP: EST3
FACP Location: Unknown 24VDC (Visual) |
The Calgary Tower is a lookout tower and tourist attraction in Downtown Calgary, Alberta. It is known for its view of the city, and its revolving restaurant. The tower is 191 meters tall, and was the tallest building in Western Canada when it opened in 1968. The fire alarm system is not original; it was installed in the 2000s.
System Specifications
FACP
The tower is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs EST's Signature addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time.
Notification Appliances
Most areas have EST "Genesis" G4-S7VM speaker/strobes (white, wall-mount, 70V, set to 15cd). The restrooms and possibly other areas have EST G1-VM remote strobes (white, wall-mount, no lettering, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the tower, mounted on EST SIGA-SB bases.