More actions
Twentytwo22 (talk | contribs) No edit summary |
No edit summary |
||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier NFS2-3030C | | FACP: Notifier NFS2-3030C | ||
FACP Location: Unknown<br />System Type: Addressable (Hybrid Manner) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC | FACP Location: Unknown<br />System Type: Addressable (Hybrid Manner) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC | ||
Line 14: | Line 14: | ||
== System Specifications == | == System Specifications == | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by a Notifier NFS2-3030C hybrid-addressable fire alarm system. | The building is protected by a Notifier NFS2-3030C hybrid-addressable fire alarm system. The panel location is unknown. The panel has several Notifier XP10-MA zone modules wired to it. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances are System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to 15cd/electromechanical). | All notification appliances are System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to 15cd/electromechanical). | ||
Line 20: | Line 20: | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
The pull stations are a mix of Edwards 270-SPO and Notifier MPS-950B conventional single-action pull stations. These are located at each exit, and in each concession stand. The 270-SPO pull stations were installed during the expansions from 1973-1987. | The pull stations are a mix of Edwards 270-SPO and Notifier MPS-950B conventional single-action pull stations. These are located at each exit, and in each concession stand. The 270-SPO pull stations were installed during the expansions from 1973-1987. | ||
=== Automatic Detection Devices === | === Automatic Detection Devices === | ||
The public washrooms have Notifier FST-851RA addressable fixed/rate-of-rise heat detectors. | The public washrooms have Notifier FST-851RA addressable fixed/rate-of-rise heat detectors. The main kitchens on each side have Notifier FST-851HA addressable fixed 190-degree F heat detectors. The smaller stands have FDD CR135 conventional fixed/rate-of-rise heat detectors. | ||
[[Category:Facilities]] | [[Category:Facilities]] | ||
[[Category:Facilities]] | [[Category:Facilities]] | ||
[[Category:Calgary]] | |||
[[Category:CFL Stadiums]] | |||
[[Category:Stadiums]] | |||
[[Category:Iconic buildings in Calgary]] |
Revision as of 20:11, 25 May 2024
System Specifications |
---|
FACP: Notifier NFS2-3030C
FACP Location: Unknown System Coding: Temporal |
McMahon Stadium is a football stadium located at in NW Calgary near Banff Trail station. It is the home of the Calgary Stampeders. This stadium was built in 1960, and renovated in 2001 and 2005. The fire alarm system was partially replaced in the 2000s, with the main FACP being upgraded in 2013.
System Specifications
FACP
The building is protected by a Notifier NFS2-3030C hybrid-addressable fire alarm system. The panel location is unknown. The panel has several Notifier XP10-MA zone modules wired to it. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are System Sensor "SpectrAlert" P1224MCA horn/strobes (red, wall-mount, set to 15cd/electromechanical).
Initiating Devices
Pull Stations
The pull stations are a mix of Edwards 270-SPO and Notifier MPS-950B conventional single-action pull stations. These are located at each exit, and in each concession stand. The 270-SPO pull stations were installed during the expansions from 1973-1987.
Automatic Detection Devices
The public washrooms have Notifier FST-851RA addressable fixed/rate-of-rise heat detectors. The main kitchens on each side have Notifier FST-851HA addressable fixed 190-degree F heat detectors. The smaller stands have FDD CR135 conventional fixed/rate-of-rise heat detectors.