Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

University of Calgary Kinesiology A: Difference between revisions

From FireAlarmPedia
No edit summary
mNo edit summary
Line 7: Line 7:
| FACP: Simplex 4100ES <br /> FACP Location: Main Entrance Vestibule <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized <br />Date of last known Upgrade: 2020 (full overhaul) <br />Year Opened: 1962
| FACP: Simplex 4100ES <br /> FACP Location: Main Entrance Vestibule <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized <br />Date of last known Upgrade: 2020 (full overhaul) <br />Year Opened: 1962
|}
|}
 
The '''University of Calagry''' is a public university located in Calgary, Alberta, Canada. This page will cover the '''Kinesiology A''' building, which opened in 1962 and underwent an expansion in 1971. The fire alarm system was installed in 2020.
The ‘’’University of Calgary’’’ is a public university located in Calgary, Alberta, Canada. This page will cover the Kinesiology A building, which opened in 1962 and underwent an expansion in 1971. The fire alarm system was installed in 2020.
==System Specifications (2020-present)==
 
==System Specifications==
====FACP====
====FACP====
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with the InfoAlarm Command Center. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The messages and/or tones are unknown at this time. The system replaced a conventional, non-voice evac 4100ES due to that system being outdated.
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with the InfoAlarm Command Center. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The messages and/or tones are unknown at this time. The system replaced a conventional, non-voice evac 4100ES due to that system being outdated.
 
====Notification Appliances====
====Notification Appliances====
All indoor notification appliances are Simplex “TrueAlert” 4906-9151 speaker/strobes (red, wall-mount). For outdoor notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount) outside the main entrance.
All indoor notification appliances are Simplex “TrueAlert” 4906-9151 speaker/strobes (red, wall-mount). For outdoor notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount) outside the main entrance.
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on 4098-9792 addressable bases.
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on 4098-9792 addressable bases.
==System Specifications (1962-2020)==
==System Specifications (1962-2020)==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 35: Line 28:
|}
|}
====FACP====
====FACP====
The building was protected by a Simplex 4100ES conventional fire alarm system. The panel was located in the main entrance vestibule, and was equipped with InfoAlarm Command Center. The system coding was temporal. This panel replaced an Edwards 6500 in 2016 to add more detectors, and was replaced in 2020 with an addressable variant with voice evacuation.  
The building was protected by a Simplex 4100ES conventional fire alarm system. The panel was located in the main entrance vestibule, and was equipped with InfoAlarm Command Center. The system coding was temporal. This panel replaced an Edwards 6500 in 2016 to add more detectors, and was replaced in 2020 with an addressable variant with voice evacuation.  
 
===== Annunciators =====
===== Annunciators =====
There is an Edwards annunciator at the entrance, model to be confirmed. It remains, but is disconnected.
There is an Edwards annunciator at the entrance, model to be confirmed. It remains, but is disconnected.
====Notification Appliances====
====Notification Appliances====
All notification appliances were Edwards “Adaptahorn” 360 horns (red, wall-mount). These were original in both wings, and were not replaced despite the age. The ones installed in the 1971 expansion had “FIRE HORN” on them. The horns were 20VDC, however the NAC voltage did not harm it. According to campus security, these horns were very loud and were one of the best-working alarms on campus! These horns lasted a whopping 58 years in service!
All notification appliances were Edwards “Adaptahorn” 360 horns (red, wall-mount). These were original in both wings, and were not replaced despite the age. The ones installed in the 1971 expansion had “FIRE HORN” on them. The horns were 20VDC.


According to campus security, these horns were very loud and were one of the best-working alarms on campus! These horns lasted 58 years in service!
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
Most pull stations were the original first-generation Edwards 270-SPO conventional single-action pull stations. Variants up to third generation 270-SPO’s could be found as deficiency replacements. Some areas had Simplex 2099-9754 conventional single-action pull stations as deficiency replacements, installed by JCI.
Most pull stations were the original first-generation Edwards 270-SPO conventional single-action pull stations. Variants up to third generation 270-SPO’s could be found as deficiency replacements. Some areas had Simplex 2099-9754 conventional single-action pull stations as deficiency replacements, installed by JCI.
====Automatic Detection Devices====
====Automatic Detection Devices====
Not known.
Not known.
[[Category:Facilities]]
[[Category:Facilities]]

Revision as of 23:24, 4 December 2023

System Specifications
FACP: Simplex 4100ES
FACP Location: Main Entrance Vestibule
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Unknown
Strobes Synchronized
Date of last known Upgrade: 2020 (full overhaul)
Year Opened: 1962

The University of Calagry is a public university located in Calgary, Alberta, Canada. This page will cover the Kinesiology A building, which opened in 1962 and underwent an expansion in 1971. The fire alarm system was installed in 2020.

System Specifications (2020-present)

FACP

The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with the InfoAlarm Command Center. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The messages and/or tones are unknown at this time. The system replaced a conventional, non-voice evac 4100ES due to that system being outdated.

Notification Appliances

All indoor notification appliances are Simplex “TrueAlert” 4906-9151 speaker/strobes (red, wall-mount). For outdoor notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount) outside the main entrance.

Initiating Devices

Pull Stations

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on 4098-9792 addressable bases.

System Specifications (1962-2020)

System Specifications
FACP: Simplex 4100ES
FACP Location: Main Entrance Vestibule
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Date of last known Upgrade: 2016
Year Decommissioned: 2020

FACP

The building was protected by a Simplex 4100ES conventional fire alarm system. The panel was located in the main entrance vestibule, and was equipped with InfoAlarm Command Center. The system coding was temporal. This panel replaced an Edwards 6500 in 2016 to add more detectors, and was replaced in 2020 with an addressable variant with voice evacuation.

Annunciators

There is an Edwards annunciator at the entrance, model to be confirmed. It remains, but is disconnected.

Notification Appliances

All notification appliances were Edwards “Adaptahorn” 360 horns (red, wall-mount). These were original in both wings, and were not replaced despite the age. The ones installed in the 1971 expansion had “FIRE HORN” on them. The horns were 20VDC.

According to campus security, these horns were very loud and were one of the best-working alarms on campus! These horns lasted 58 years in service!

Initiating Devices

Pull Stations

Most pull stations were the original first-generation Edwards 270-SPO conventional single-action pull stations. Variants up to third generation 270-SPO’s could be found as deficiency replacements. Some areas had Simplex 2099-9754 conventional single-action pull stations as deficiency replacements, installed by JCI.

Automatic Detection Devices

Not known.