Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Aldred Centre (SAIT): Difference between revisions

From FireAlarmPedia
No edit summary
(Added alarm info!)
Line 8: Line 8:
FACP Location: Unknown <br />System Type: Addressable (Two-Stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70VRMS (audible) <br> 24VDC (visual)  
FACP Location: Unknown <br />System Type: Addressable (Two-Stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70VRMS (audible) <br> 24VDC (visual)  


System Coding: Unknown
System Coding: 20BPM (First Stage)
 
Temporal (GA)


Strobes Synchronized: Yes<br />Date of last known Upgrade: N/A <br />Year Opened: 2012
Strobes Synchronized: Yes<br />Date of last known Upgrade: N/A <br />Year Opened: 2012
Line 15: Line 17:
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs EST's Signature-series addressable protocol, and is configured for two-stage operation. The system is equipped with voice evacuation. The messages and/or tones are unknown at this time.
The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs EST's Signature-series addressable protocol, and is configured for two-stage operation. The system is equipped with voice evacuation. The first stage tone is 20BPM, followed by temporal in general alarm.
====Notification Appliances====
====Notification Appliances====
The main notification appliances are EST "Genesis" G4R-S7VM speaker/strobes (red, wall-mount, no lettering). There are also EST G4R-S7 remote speakers (red, wall-mount) for additional sound coverage.
The main notification appliances are EST "Genesis" G4R-S7VM speaker/strobes (red, wall-mount, no lettering). There are also EST G4R-S7 remote speakers (red, wall-mount) for additional sound coverage.
Line 23: Line 25:
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the facility, mounted on EST SIGA-SB bases.
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the facility, mounted on EST SIGA-SB bases.
[[]
 
== Message Script ==
The tone you heard confirms there is an emergency in the building.  You are to leave the building by the nearest exit or exit stairway.  Do not use the elevators.

Revision as of 09:10, 5 August 2023

System Specifications
FACP: Edwards EST3

FACP Location: Unknown
System Type: Addressable (Two-Stage)
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (audible)
24VDC (visual)

System Coding: 20BPM (First Stage)

Temporal (GA)

Strobes Synchronized: Yes
Date of last known Upgrade: N/A
Year Opened: 2012

Aldred Centre is an education building located in the Southern Alberta Institute of Technology, in Calgary, Alberta, Canada. It was built in 2012, and has the original system.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs EST's Signature-series addressable protocol, and is configured for two-stage operation. The system is equipped with voice evacuation. The first stage tone is 20BPM, followed by temporal in general alarm.

Notification Appliances

The main notification appliances are EST "Genesis" G4R-S7VM speaker/strobes (red, wall-mount, no lettering). There are also EST G4R-S7 remote speakers (red, wall-mount) for additional sound coverage.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the facility, mounted on EST SIGA-SB bases.

Message Script