The building is protected by an EST 6616 16-zone conventional fire alarm system. The panel is located across from the front desk. This panel has suffered a main board failure, and is stuck in alarm. Therefore, the system is inoperable, and should be replaced immediately. The system coding is likely continuous.
The building is protected by an EST 6616 16-zone conventional fire alarm system. The panel is located across from the front desk. This panel has suffered a main board failure, and is stuck in alarm. Therefore, the system is inoperable, and should be replaced immediately. The system coding is likely continuous.
====Notification Appliances====
====Notification Appliances====
Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong). There are also EST "Integrity" 202-5A-T remote strobes (red, wall-mount, 15cd) throughout the hotel. One strobe is resting on a cutout of a ceiling tile, and therefore does not have proper coverage.
Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong). Captain's Pub has an Edwards 439D-10AWC vibrating bell (10" gong) for additional coverage. There are also EST "Integrity" 202-5A-001 remote strobes (red, wall-mount, 15cd) throughout the hotel. One strobe is resting on a cutout of a ceiling tile, and therefore does not have proper coverage.
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====

Revision as of 00:23, 11 December 2023

System Specifications
FACP: EST 6616 (Inoperable)

FACP Location: Main Lobby
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR

System Coding: Continuous
Date of last known Upgrade: N/A
Year Opened: Early 1990s

Anchor Inn and Suites is a hotel located in Twillingate, Newfoundland. It also contains Georgie's Restaurant. The building was built in the early 1990s, and has the original fire alarm system.

System Specifications

FACP

The building is protected by an EST 6616 16-zone conventional fire alarm system. The panel is located across from the front desk. This panel has suffered a main board failure, and is stuck in alarm. Therefore, the system is inoperable, and should be replaced immediately. The system coding is likely continuous.

Notification Appliances

Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong). Captain's Pub has an Edwards 439D-10AWC vibrating bell (10" gong) for additional coverage. There are also EST "Integrity" 202-5A-001 remote strobes (red, wall-mount, 15cd) throughout the hotel. One strobe is resting on a cutout of a ceiling tile, and therefore does not have proper coverage.

Initiating Devices

Pull Stations

All pull stations are Edwards 270-SPO conventional single-action pull stations.

Automatic Detection Devices

There are Edwards 6249C conventional 4-wire ionization smoke detectors throughout the hotel.