The Approach Hotel - Building B: Difference between revisions

From FireAlarmPedia
mNo edit summary
mNo edit summary
Line 5: Line 5:
|  
|  
|-
|-
| FACP: GE FireShield Plus
| FACP: GE FireShield Plus FSP1004G
FACP Location: Lobby<br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR  
FACP Location: Lobby<br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR  


Line 13: Line 13:
== System Specifications (late 80s-present) ==
== System Specifications (late 80s-present) ==
==== FACP ====
==== FACP ====
The building is protected by a GE FireShield Plus conventional fire alarm system. The panel is located in the lobby, and is specifically model FSP1004G (10 zones) and is equipped with the DACT. It replaced an Edwards 2280 in 2011. The system coding is likely temporal.
The building is protected by a GE FireShield Plus FSP1004G onventional fire alarm system. The panel is located in the lobby and is equipped with the DACT. The system coding is likely temporal.
 
The panel replaced an Edwards 2280 in 2011.
==== Notification Appliances ====
==== Notification Appliances ====
All notification appliances are Edwards 439D-10AWC vibrating bells (10" gong).  
All notification appliances are Edwards 439D-10AWC vibrating bells (10" gong).  
Line 20: Line 22:
All pull stations are Edwards 270-SPO pull stations, installed in the late 80s (no FIRE ALARM, 270A font)[[File:Rare 270-SPO.jpg|thumb|Photo of the exact pull station used]]
All pull stations are Edwards 270-SPO pull stations, installed in the late 80s (no FIRE ALARM, 270A font)[[File:Rare 270-SPO.jpg|thumb|Photo of the exact pull station used]]
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
All smoke detectors are Edwards 6249C photoelectric smoke detectors, and the heat detectors are Edwards 281C fixed-temperature/rate-of-rise heat detectors.  
All smoke detectors are Edwards 6250C ionization smoke detectors.
 
Some areas have Edwards 281C fixed-temperature/rate-of-rise heat detectors.  
[[Category:Facilities]]
[[Category:Facilities]]

Revision as of 00:39, 4 February 2024

System Specifications
FACP: GE FireShield Plus FSP1004G

FACP Location: Lobby
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR

System Coding: Temporal?
Date of last known Upgrade: 2011
Year Opened: 1982

The Approach Hotel is a hotel in Panorama Mountain Resort, BC that consists of two buildings. It is located at 2040 Summit Drive. This page will cover Building B, which houses Fireside Cafe & Lounge, and the fitness rooms and a spa. It was built in 1982 as Pine Inn North, and was renamed The Approach Hotel in 2022. The fire alarm system survived the renovations; the system was mostly installed in the late 1980s.

System Specifications (late 80s-present)

FACP

The building is protected by a GE FireShield Plus FSP1004G onventional fire alarm system. The panel is located in the lobby and is equipped with the DACT. The system coding is likely temporal.

The panel replaced an Edwards 2280 in 2011.

Notification Appliances

All notification appliances are Edwards 439D-10AWC vibrating bells (10" gong).

Initiating Devices

Pull Stations

All pull stations are Edwards 270-SPO pull stations, installed in the late 80s (no FIRE ALARM, 270A font)

Photo of the exact pull station used

Automatic Detection Devices

All smoke detectors are Edwards 6250C ionization smoke detectors.

Some areas have Edwards 281C fixed-temperature/rate-of-rise heat detectors.