(Found the building year! system is not original) |
|||
Line 15: | Line 15: | ||
==System Specifications (mid 1990s-present)== | ==System Specifications (mid 1990s-present)== | ||
====FACP==== | ====FACP==== | ||
The building is protected by an EST 6616 16-zone conventional fire alarm system. The panel is located across from the front desk. This panel has suffered a main board failure, and is stuck in alarm. Therefore, the system is | The building is protected by an EST 6616 16-zone conventional fire alarm system. The panel is located across from the front desk. This panel has suffered a main board failure, and is stuck in alarm. Therefore, the system is no longer functional, and should be replaced immediately. The system coding is likely continuous. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong). Captain's Pub has an Edwards 439D-10AWC vibrating bell (10" gong) for additional coverage. There are also EST "Integrity" 202-5A-001 remote strobes (red, wall-mount, 15cd) throughout the hotel. One strobe is resting on a cutout of a ceiling tile, and therefore does not have proper coverage. | Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong). Captain's Pub has an Edwards 439D-10AWC vibrating bell (10" gong) for additional coverage. There are also EST "Integrity" 202-5A-001 remote strobes (red, wall-mount, 15cd) throughout the hotel. One strobe is resting on a cutout of a ceiling tile, and therefore does not have proper coverage. |
Revision as of 23:28, 10 December 2023
System Specifications |
---|
FACP: EST 6616 (Inoperable)
FACP Location: Main Lobby System Coding: Continuous Strobes Synchronized: No |
Anchor Inn and Suites is a hotel located in Twillingate, Newfoundland. It also contains Georgie's Restaurant. The building was built in 1968, and the fire alarm system was upgraded in the mid-1990s. The panel has failed, and the system is therefore inoperable.
System Specifications (mid 1990s-present)
FACP
The building is protected by an EST 6616 16-zone conventional fire alarm system. The panel is located across from the front desk. This panel has suffered a main board failure, and is stuck in alarm. Therefore, the system is no longer functional, and should be replaced immediately. The system coding is likely continuous.
Notification Appliances
Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong). Captain's Pub has an Edwards 439D-10AWC vibrating bell (10" gong) for additional coverage. There are also EST "Integrity" 202-5A-001 remote strobes (red, wall-mount, 15cd) throughout the hotel. One strobe is resting on a cutout of a ceiling tile, and therefore does not have proper coverage.
Initiating Devices
Pull Stations
All pull stations are Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices
There are Edwards 6249C conventional 4-wire ionization smoke detectors throughout the hotel.
Bonus Information
- The restaurant in this hotel, Georgie's, is very good, and is highly recommended by the staff of this Wiki.
- This building has the most fire alarm issues ever spotted by the staff of this wiki.
[[]