==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
=====Dressing Room Hallway===== | =====Dressing Room Hallway===== | ||
All notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd) mounted on Edwards G1TR trim plates (red). These were installed in the mid-2000s for some unknown reason. | All notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd) mounted on Edwards G1TR trim plates (red). | ||
These were installed in the mid-2000s for some unknown reason, likely for volume concerns, however this is a code violation. | |||
=====Arena/Lobby===== | =====Arena/Lobby===== | ||
The main lobby has an Edwards "Durabel" 6100D vibrating bell (6" gong), which remained from the previous system. | The main lobby has an Edwards "Durabel" 6100D vibrating bell (6" gong), which remained from the previous system. | ||
Line 26: | Line 28: | ||
Deficiency replacements are: | Deficiency replacements are: | ||
* Mircom MS-401 conventional single-action pull stations in several areas | * Mircom MS-401 conventional single-action pull stations in several areas | ||
* Notifier NFM-950B conventional single-action pull station next to the main entrance | * Notifier NFM-950B conventional single-action pull station next to the main entrance |
Revision as of 22:53, 6 February 2024
[[Category:Arena]
System Specifications |
---|
FACP: Edwards 2280 FACP Location: Unknown System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous/Temporal Date of last known Upgrade: Mid-late 2000s Year Opened: 1960 |
Cochrane Arena is an ice hockey arena located at 609 Fourth Avenue North, in Cochrane, Alberta, Canada. The arena opened in 1960, and was the first arena in the town of Cochrane. The fire alarm system was mostly upgraded in 1990, with parts ranging from the early 1980s to the 2010s.
System Specifications (1990-present)
FACP
The building is protected by an Edwards 2280 conventional fire alarm system. The panel location is unknown, and was installed in 1990. The system coding is continuous for all bells, and the horn/strobes are self-coded to temporal.
Annunciators
There is an Edwards annunciator at the main entrance, model unknown.
Notification Appliances
Dressing Room Hallway
All notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd) mounted on Edwards G1TR trim plates (red).
These were installed in the mid-2000s for some unknown reason, likely for volume concerns, however this is a code violation.
Arena/Lobby
The main lobby has an Edwards "Durabel" 6100D vibrating bell (6" gong), which remained from the previous system.
The main arena has a Wheelock MB-G6-24 motor bell (6" gong), as a deficiency replacement for a Durabel.
Initiating Devices
Pull Stations
Most pull stations are Edwards 270-SPO conventional single-action pull stations, installed with the 2280.
Deficiency replacements are:
- Mircom MS-401 conventional single-action pull stations in several areas
- Notifier NFM-950B conventional single-action pull station next to the main entrance
- Notifier MPS-950B conventional single-action pull station in the main arena.
Automatic Detection Devices
There are Edwards EC30U-3 conventional photoelectric smoke detectors throughout the building. These were installed in the mid-2010s.
Code Violations
This building has horn/strobes and bells mixed. This is against code, as according to CAN-ULC codes, the sound of an alarm signal must be uniform. [[]