| FACP: Notifier NFS-320C <br />FACP Location: Basement Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (alert) <br> Temporal ( | | FACP: Notifier NFS-320C <br />FACP Location: Basement Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (alert) <br> Temporal (alarm) <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2015 <br />Year Opened: Early 1970s | ||
|} | |} | ||
Revision as of 14:27, 17 March 2024
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Basement Electrical Room System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (alert) Temporal (alarm) Strobes Synchronized: No Date of last known Upgrade: 2015 Year Opened: Early 1970s |
AgeCare Glenmore is a retirement home located at 1729 90 Ave SW, Calgary, Alberta. The building opened in the early 1970s as the Beverly Care Centre, expanded in 1984 and in the early 1990s. The fire alarm system was upgraded in the early 1990s, with a minor upgrade in 2015.
System Specifications
FACP
The building is protected by a Notifier NFS-320C conventional fire alarm system. The panel is located in the basement electrical room. The panel has several Notifier XP6-MA zone cards to accommodate the conventional devices. The system configured for two-stage operation. The alert signal is 20BPM, followed by Temporal as the alarm signal.
Annunciators
There is a Notifier LCD2-80 annunciator in the main entrance vestibule.
Notification Appliances
Most notification appliances are Edwards 439D-6AWC vibrating bells (6” gong), mounted behind grilles to amplify the sound.
There is one Simplex 2901-9723 motor bell (6” gong) as a deficiency replacement.
Each bell has an Edwards 802-2B remote strobe (red, wall-mount) mounted next to it.
Initiating Devices
Pull Stations
All pull stations are Edwards 270-GAO conventional dual-stage single-action pull stations.
Automatic Detection Devices
There are System Sensor C2W-BA conventional 2-wire photoelectric smoke detectors throughout the building.