(replacing panels and smokes are a common trend) |
No edit summary |
||
Line 7: | Line 7: | ||
| FACP: Simplex 4100ES <br />FACP Location: Main Entrance <br />System Type: Hybrid-Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2015 <br />Year Opened: 1993 | | FACP: Simplex 4100ES <br />FACP Location: Main Entrance <br />System Type: Hybrid-Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2015 <br />Year Opened: 1993 | ||
|} | |} | ||
'''Mitford School''' is a middle school located at 110 Quigley Drive, in Cochrane, Alberta, Canada. The school is part of the Rocky View School District. The school opened in 1993, and the fire alarm system is mostly original. | |||
'''Mitford School''' is a middle school located at 110 Quigley Drive, in Cochrane, Alberta, Canada. | |||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Simplex 4100ES hybrid-addressable fire alarm system. | The building is protected by a Simplex 4100ES hybrid-addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is continuous. <br>This panel was installed in 2015 and replaced a Simplex 4002. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
Most areas have Simplex 2901-9722 motor bells (10” gong). | Most areas have Simplex 2901-9722 motor bells (10” gong). <br>Most bells are mounted behind grilles, and are mounted on Simplex 4903-9101 strobe plates in one hallway. <br>One classroom has a Simplex 2901-9723 motor bell (6” gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd). <br>For outdoor notification, there are Simplex 2901-9722 motor bells (10” gong), with one Simplex 2901-9724 motor bell (10” gong) as a deficiency replacement. | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Simplex 2099-9754 conventional single-action pull stations. | All pull stations are Simplex 2099-9754 conventional single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases. | There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases. | ||
[[Category:Alberta]] | |||
[[Category:Schools]] |
Revision as of 20:20, 25 May 2024
System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Main Entrance System Type: Hybrid-Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2015 Year Opened: 1993 |
Mitford School is a middle school located at 110 Quigley Drive, in Cochrane, Alberta, Canada. The school is part of the Rocky View School District. The school opened in 1993, and the fire alarm system is mostly original.
System Specifications
FACP
The building is protected by a Simplex 4100ES hybrid-addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is continuous.
This panel was installed in 2015 and replaced a Simplex 4002.
Notification Appliances
Most areas have Simplex 2901-9722 motor bells (10” gong).
Most bells are mounted behind grilles, and are mounted on Simplex 4903-9101 strobe plates in one hallway.
One classroom has a Simplex 2901-9723 motor bell (6” gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd).
For outdoor notification, there are Simplex 2901-9722 motor bells (10” gong), with one Simplex 2901-9724 motor bell (10” gong) as a deficiency replacement.
Initiating Devices
Pull Stations
All pull stations are Simplex 2099-9754 conventional single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases.