More actions
mNo edit summary |
No edit summary |
||
Line 36: | Line 36: | ||
Most areas have Fire Detection Devices CR135 conventional 135°F fixed/rate-of-rise heat detectors. | Most areas have Fire Detection Devices CR135 conventional 135°F fixed/rate-of-rise heat detectors. | ||
==Code Violations== | ==Code Violations== | ||
This building has horn/strobes and bells mixed. This is against code, as according to CAN-ULC codes, the sound of an alarm signal must be uniform | This building has horn/strobes and bells mixed. This is against code, as according to CAN-ULC codes, the sound of an alarm signal must be uniform | ||
[[Category:Calgary]] | |||
[[Category:Commercial]] |
Revision as of 19:09, 23 May 2024
System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Main Entrance System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: 2023 Year Opened: 1979 |
Centre Eleven is an office building located at 1121 Centre Street Northwest, in Calgary, Alberta, Canada. The building opened in 1979, and the fire alarm system is partially original, with a panel replacement occurring in 2023.
System Specifications (1979-present)
FACP
The building is protected by a Mircom FX-2000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is temporal.
The panel replaced a Mircom FA-1000 in 2023
Annunciators
There is a Mircom RAX-LCD annunciator in a Mircom BB-1001 enclosure at the dance studio entrance.
Booster Panels
There is an Edwards BPS10A booster power supply in a closet on the first floor.
Notification Appliances
The notification appliances are primarily a mix of Mircom BL-6A/BL-6B motor bells (6” gong) and Mircom BL-10A/BL-10B motor bells (10” gong).
The main floor back exit has an Edwards 439D-6AWC vibrating bell (6” gong) installed in 2021 as a deficiency replacement.
There is an Edwards 439D-6AWC vibrating bell (6” gong) mounted on an Edwards 403-5A-R strobe plate (15cd) in a first floor unit.
The parkade has Wheelock MB-G6-24 motor bells (6" gong).
The first floor of the dance studio has Mircom FHS-400-RR horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations but one are Edwards 270-SPO conventional single-action pull stations.
There is an Edwards 274-111 conventional single-action pull station in a first floor unit.
Automatic Detection Devices
There are System Sensor "i3" C2W-BA conventional 2-wire photoelectric smoke detectors in some areas.
Most areas have Fire Detection Devices CR135 conventional 135°F fixed/rate-of-rise heat detectors.
Code Violations
This building has horn/strobes and bells mixed. This is against code, as according to CAN-ULC codes, the sound of an alarm signal must be uniform