| FACP: Simplex 4100ES <br />FACP Location: Main Entrance <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br>24VDC (Visual) <br />System Coding: | | FACP: Simplex 4100ES <br />FACP Location: Main Entrance <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br>24VDC (Visual) <br />System Coding: Slow Whoop + Custom Message<br>Strobes Synchronized: No <br />Date of last known Upgrade: 2023<br />Year Opened: 1996 | ||
|} | |} | ||
The '''Northern Alberta Institute of Technology''' is a technical college/trades school located in Edmonton, Alberta, Canada. This page will cover the South Learning Centre/Shaw Theatre building, located at 10604 Princess Elizabeth Ave NW #10824, in Edmonton, Alberta, Canada. The building opened in 1996, and the fire alarm system is mostly original, with a recent upgrade. | The '''Northern Alberta Institute of Technology''' is a technical college/trades school located in Edmonton, Alberta, Canada. This page will cover the South Learning Centre/Shaw Theatre building, located at 10604 Princess Elizabeth Ave NW #10824, in Edmonton, Alberta, Canada. The building opened in 1996, and the fire alarm system is mostly original, with a recent upgrade. | ||
==System Specifications (1996-present)== | ==System Specifications (1996-present)== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with the Color ES touchscreen interface. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The evacuation signal is | The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with the Color ES touchscreen interface. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The evacuation signal is slow whoop followed by a custom message.<br>This panel was installed in 2023, replacing a 4100ES with in turn replaced a Simplex 4100+ in 2016. This panel is installed in the 4100+ cabinet. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
The South Learning Centre has Wheelock E-9070-LS-24-CFW speaker/strobes (white, ceiling-mount, 70V, 15cd). <br>The Shaw Theatre has Simplex 2902-9711 remote speakers (red, wall-mount) mounted on Wheelock VLPS-24 strobe plates (1.5cd). | The South Learning Centre has Wheelock E-9070-LS-24-CFW speaker/strobes (white, ceiling-mount, 70V, 15cd). <br>The Shaw Theatre has Simplex 2902-9711 remote speakers (red, wall-mount) mounted on Wheelock VLPS-24 strobe plates (1.5cd). | ||
Line 22: | Line 22: | ||
====Modules==== | ====Modules==== | ||
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
== Voice Evac Message Script == | |||
"May I have your attention please! May I have your attention please! There has been a fire alarm condition reported in the building. While this being verified, please leave the building by the nearest exit or exit stairway. Do not use the elevators." |
Revision as of 18:31, 10 April 2024
System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Slow Whoop + Custom Message Strobes Synchronized: No Date of last known Upgrade: 2023 Year Opened: 1996 |
The Northern Alberta Institute of Technology is a technical college/trades school located in Edmonton, Alberta, Canada. This page will cover the South Learning Centre/Shaw Theatre building, located at 10604 Princess Elizabeth Ave NW #10824, in Edmonton, Alberta, Canada. The building opened in 1996, and the fire alarm system is mostly original, with a recent upgrade.
System Specifications (1996-present)
FACP
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with the Color ES touchscreen interface. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The evacuation signal is slow whoop followed by a custom message.
This panel was installed in 2023, replacing a 4100ES with in turn replaced a Simplex 4100+ in 2016. This panel is installed in the 4100+ cabinet.
Notification Appliances
The South Learning Centre has Wheelock E-9070-LS-24-CFW speaker/strobes (white, ceiling-mount, 70V, 15cd).
The Shaw Theatre has Simplex 2902-9711 remote speakers (red, wall-mount) mounted on Wheelock VLPS-24 strobe plates (1.5cd).
For exterior notification, there is a Simplex 2902-9711 speaker outside the entrance.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations. These replaced Simplex 4099-9001 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases.
There are Simplex 4098-9756 addressable photoelectric duct smoke detectors on all air handling units, with Simplex 2098-9808 remote indicators mounted on the drop ceiling below each detector.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
Voice Evac Message Script
"May I have your attention please! May I have your attention please! There has been a fire alarm condition reported in the building. While this being verified, please leave the building by the nearest exit or exit stairway. Do not use the elevators."