| FACP: Edwards EST3 <br /> FACP Location: | | FACP: Edwards EST3 <br /> FACP Location: Main Floor Office CACF (Main Node)<br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: 20BPM 1kHz (First Stage) <br> Temporal 1kHz (GA) <br> Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2010s<br />Year Opened: 2009 | ||
|} | |} | ||
'''Hotel Le Germain Calgary''' is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The hotel opened in 2010 | '''Hotel Le Germain Calgary''' is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The building was built in 2009, and the hotel opened in 2010; the fire alarm system is original. | ||
The building is also connected to an office tower and Le Germain Residences (108 9 Ave SW). The fire alarm system monitors both of these buildings. | |||
==System Specifications (2009-present)== | ==System Specifications (2009-present)== | ||
====FACP==== | ====FACP==== | ||
The | The buildings are protected by an Edwards EST3 addressable fire alarm system. The system is a network with 7 nodes, see list below. The system runs Edwards’ Signature-series addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is a 20BPM tone, followed by a temporal tone in general alarm. No messages are played. | ||
Panels are in the following locations: | |||
* Main Floor Office CACF (Main Node) | |||
* Office Floor 9 | |||
* Parkade P0 Electrical Room | |||
* Hotel Main Floor CACF | |||
* Hotel 10th Floor Electrical Room | |||
* Condo 18th Floor Electrical Room | |||
===== Annunciators ===== | |||
There are Edwards EST 3-LCDANN LCD annunciators with LCDXL1 displays in the main floor office CACF, and behind the hotel front desk. | |||
====Notification Appliances==== | ====Notification Appliances==== | ||
=====Common Areas===== | =====Common Areas & Offices===== | ||
All notification appliances are Edwards 965- | All notification appliances are Edwards 965-3A-8RW speaker/strobes (white, ceiling-mount, 8” round, 30cd, 70V). | ||
There is an EST "Genesis" G4R-S7VM speaker/strobe (red, wall-mount, no marking, set to 15cd) in one renovated office unit. | |||
There is also an EST "Genesis" G1R-VM remote strobe (red, wall-mount, no marking, set to 15cd) in the 2nd floor office area. | |||
=====Guest Rooms===== | =====Guest Rooms===== | ||
All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway. | All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway. | ||
Line 20: | Line 39: | ||
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations. | All pull stations are EST SIGA-270P addressable two-stage single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the | There are EST SIGA-PS addressable photoelectric smoke detectors throughout the buildings. | ||
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the restaurant kitchen and garbage chute. | |||
All detectors are mounted on SIGA-SB bases. | |||
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on the air handling units. | |||
==== Modules ==== | |||
There are EST SIGA-CT1 addressable monitor modules and EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches and kitchen suppression system. | |||
There are EST SIGA-CR addressable relays for dampers, door holders, and fans. | |||
There are EST SIGA-IM isolator modules on the SLCs. |
Revision as of 23:06, 26 April 2024
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Main Floor Office CACF (Main Node) System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: 20BPM 1kHz (First Stage) Temporal 1kHz (GA) Strobes Synchronized: Yes, EST Date of last known Upgrade: 2010s Year Opened: 2009 |
Hotel Le Germain Calgary is a large upscale hotel located at 899 Centre Street South, in Downtown Calgary, Alberta, Canada. The hotel is known for its spa, and has a restaurant and bar on site. The hotel has a 4 star rating, and is very highly reviewed. The building was built in 2009, and the hotel opened in 2010; the fire alarm system is original.
The building is also connected to an office tower and Le Germain Residences (108 9 Ave SW). The fire alarm system monitors both of these buildings.
System Specifications (2009-present)
FACP
The buildings are protected by an Edwards EST3 addressable fire alarm system. The system is a network with 7 nodes, see list below. The system runs Edwards’ Signature-series addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The first stage signal is a 20BPM tone, followed by a temporal tone in general alarm. No messages are played.
Panels are in the following locations:
- Main Floor Office CACF (Main Node)
- Office Floor 9
- Parkade P0 Electrical Room
- Hotel Main Floor CACF
- Hotel 10th Floor Electrical Room
- Condo 18th Floor Electrical Room
Annunciators
There are Edwards EST 3-LCDANN LCD annunciators with LCDXL1 displays in the main floor office CACF, and behind the hotel front desk.
Notification Appliances
Common Areas & Offices
All notification appliances are Edwards 965-3A-8RW speaker/strobes (white, ceiling-mount, 8” round, 30cd, 70V).
There is an EST "Genesis" G4R-S7VM speaker/strobe (red, wall-mount, no marking, set to 15cd) in one renovated office unit.
There is also an EST "Genesis" G1R-VM remote strobe (red, wall-mount, no marking, set to 15cd) in the 2nd floor office area.
Guest Rooms
All guest rooms have Edwards 965-1A-4RW remote speakers (white, ceiling-mount, 4” round, 70V) mounted near the doorway.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the buildings.
There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the restaurant kitchen and garbage chute.
All detectors are mounted on SIGA-SB bases.
There are EST "SuperDuct" SIGA-SD addressable photoelectric duct smoke detectors on the air handling units.
Modules
There are EST SIGA-CT1 addressable monitor modules and EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system's tamper and flow switches and kitchen suppression system.
There are EST SIGA-CR addressable relays for dampers, door holders, and fans.
There are EST SIGA-IM isolator modules on the SLCs.