Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Calgary Soccer Centre: Difference between revisions

From FireAlarmPedia
(Page overhauled! Now all under one setion.)
mNo edit summary
Line 16: Line 16:


The main building is wired as conventional, while the annex is addressable.
The main building is wired as conventional, while the annex is addressable.
===== Annunciators =====
===== Annunciators =====
There is a Notifier LCD2-80 LCD annunciator in the main building's entrance vestibule.
There is a Notifier LCD2-80 LCD annunciator in the main building's entrance vestibule.
===== Booster Panels =====
===== Booster Panels =====
There are Notifier ACPS-610 6/10 amp power supplies in the main building entrance vestibule and annex electrical room.
There are Notifier ACPS-610 6/10 amp power supplies in the main building entrance vestibule and annex electrical room.
====Notification Appliances====
====Notification Appliances====
==== Main Building ====
==== Main Building ====
All notification appliances but one are Edwards 439D-10AWC vibrating bells (10” gong).
All notification appliances but one are Edwards 439D-10AWC vibrating bells (10” gong).
There is a Mircom BL-10B motor bell (10" gong) on the lower level as a deficiency replacement.\


There is a Mircom BL-10B motor bell (10" gong) on the lower level as a deficiency replacement.
===== Annex =====
===== Annex =====
Most notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).  
Most notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).  


The fields have System Sensor PC2WA horn/strobes (white, ceiling-mount, set to 15cd).
The fields have System Sensor PC2WA horn/strobes (white, ceiling-mount, set to 15cd).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
Line 42: Line 37:
All pull stations in the annex are Notifier N-MPS-SA addressable single-action pull stations.
All pull stations in the annex are Notifier N-MPS-SA addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
===== Main Building =====
===== Main Building =====
There are Edwards 284C conventional 197°F fixed/rate-of-rise heat detectors in the furnace rooms, electrical rooms, and generator rooms. These are NOS from 1989.
There are Edwards 284C conventional 197°F fixed/rate-of-rise heat detectors in the furnace rooms, electrical rooms, and generator rooms. These are NOS from 1989.
Line 49: Line 43:


The air handling units have Edwards SD-2W conventional photoelectric duct smoke detectors.  
The air handling units have Edwards SD-2W conventional photoelectric duct smoke detectors.  
===== Annex =====
===== Annex =====
There are Notifier FSP-851A addressable photoelectric smoke detectors in the link between the two buildings.
There are Notifier FSP-851A addressable photoelectric smoke detectors in the link between the two buildings.

Revision as of 22:48, 27 April 2024

System Specifications
FACP: Notifier NFS2-640C
FACP Location: Annex Entrance
System Type: Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous (main building)

Temporal (annex)
Strobes Synchronized: Yes, SS
Date of last known Upgrade: 2014
Year Opened: 1992


Calgary Soccer Centre is a fieldhouse located at 7000 48 St SE, Calgary, Alberta, Canada. There are two buildings here. One is the main building, built in 1992. The other is the annex, built in 2014. The fire alarm system was upgraded in 2014, and remains mostly original in each part.

System Specifications (1990/2014-present)

FACP

The building is protected by a Notifier NFS2-640C hybrid-addressable fire alarm system. The panel is located in the annex entrance vestibule. The system runs Notifier’s FlashScan addressable protocol, and the system coding is continuous in the main building, and temporal in the annex.

The main building is wired as conventional, while the annex is addressable.

Annunciators

There is a Notifier LCD2-80 LCD annunciator in the main building's entrance vestibule.

Booster Panels

There are Notifier ACPS-610 6/10 amp power supplies in the main building entrance vestibule and annex electrical room.

Notification Appliances

Main Building

All notification appliances but one are Edwards 439D-10AWC vibrating bells (10” gong).

There is a Mircom BL-10B motor bell (10" gong) on the lower level as a deficiency replacement.

Annex

Most notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).

The fields have System Sensor PC2WA horn/strobes (white, ceiling-mount, set to 15cd).

Initiating Devices

Pull Stations

Most pull stations in the main building are Edwards 275-C111 conventional single-action pull stations.

Some areas have Edwards 270-SPO conventional single-action pull stations as deficiency replacements.

All pull stations in the annex are Notifier N-MPS-SA addressable single-action pull stations.

Automatic Detection Devices

Main Building

There are Edwards 284C conventional 197°F fixed/rate-of-rise heat detectors in the furnace rooms, electrical rooms, and generator rooms. These are NOS from 1989.

There is a System Sensor 2151A conventional photoelectric smoke detector in Storage Room 8, mounted on a System Sensor B210LPA base.

The air handling units have Edwards SD-2W conventional photoelectric duct smoke detectors.

Annex

There are Notifier FSP-851A addressable photoelectric smoke detectors in the link between the two buildings.

The mechanical and electrical rooms have Notifier FST-851RA addressable 135°F fixed/rate-of-rise heat detectors.

All detectors are mounted on System Sensor B210LPA bases.

There are Notifier FSB-200A addressable reflective beam smoke detectors in high ceilings.

There are System Sensor DNRA duct smoke detectors with Notifier FSP-851A addressable photoelectric heads on all air handling units, wired to System Sensor RTS151KEY keyswitches.