===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Notifier MPS-950B conventional single-action pull stations. The ones in the gymnasium are fitted with MPS-DALK dual-action levers to prevent false alarms. The air handling room and the theatre have Notifier NFM-950B conventional pull stations. All stations are attached to Notifier FMM-101A addressable monitor modules, directly behind the stations. A couple of classrooms have Notifier NBG-12LX addressable dual-action pull stations.  
All pull stations are Notifier MPS-950B conventional single-action pull stations. The ones in the gymnasium are fitted with MPS-DALK dual-action levers to prevent false alarms.
 
The air handling room and the theatre have Notifier NFM-950B conventional pull stations.
 
All stations are attached to Notifier FMM-101A addressable monitor modules, directly behind the stations.
 
A couple of classrooms have Notifier NBG-12LX addressable dual-action pull stations.  
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA low-profile bases. The air handling units mostly have Notifier FSD-751PLA addressable photoelectric smoke detectors, and a couple have System Sensor D1420A conventional photoelectric 4-wire duct smoke detectors, wired to Notifier FMM-101A modules. There is also a sprinkler system with waterflow.
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA low-profile bases.  
 
The air handling units mostly have Notifier FSD-751PLA addressable photoelectric smoke detectors, and a couple have System Sensor D1420A conventional photoelectric 4-wire duct smoke detectors, wired to Notifier FMM-101A modules.
==== Modules ====
==== Modules ====
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system flow switches.
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system flow switches.


[[]
[[]
[[Category:Schools]]
[[Category:British Columbia]]

Revision as of 15:11, 25 May 2024

System Specifications
FACP: Notifier NFS2-640C
FACP Location: Main Electrical Room
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, Wheelock
Date of last known Upgrade: 2023
Year Opened: 2007

Ecole John Stubbs Memorial School is an elementary/middle school located at 301 Zealous Crescent, in Colwood, British Columbia, Canada. The school opened in 2007, and the fire alarm system is mostly original.

System Specifications (2007-present)

FACP

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in the main electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.

The NFS2-640C replaced the original Notifier NFS-640C in 2022.

Annunciators

There is a Notifier LCD-80TM annunciator with a custom graphic at the main entrance.

Notification Appliances

All audible notification appliances are Wheelock MB-G10-24 motor bells (10” gong). These are mounted remotely in most areas, and on Wheelock RSSP-24MCW strobe plates (set to 15cd) in areas with higher noise levels.

Three of these were recently replaced with Mircom BL-10B motor bells (10" gong), as deficiency replacements. There are two Edwards MB10-24 motor bells (10" gong) on the existing aforementioned strobe plates in the lobby and air handling room as deficiency replacements.

The following bells are installed as deficiency replacements remotely

  • Edwards MB10-24 motor bells (10" gong)
  • Notifier KMS-10-24A motor bell (10" gong)
  • Simplex 2901-9724 (10" gong)
  • Mircom BL-10B (10" gong) previously installed on the second floor.

All classrooms except for one contain System Sensor "SpectrAlert" S1224MCA remote strobes (red, wall-mount, set to 15cd).

The other classroom, and the washrooms have System Sensor "SpectrAlert Advance" SRA remote strobes (red, wall-mount, set to 15cd); the one in the classroom is a deficiency replacement.

Initiating Devices

Pull Stations

All pull stations are Notifier MPS-950B conventional single-action pull stations. The ones in the gymnasium are fitted with MPS-DALK dual-action levers to prevent false alarms.

The air handling room and the theatre have Notifier NFM-950B conventional pull stations.

All stations are attached to Notifier FMM-101A addressable monitor modules, directly behind the stations.

A couple of classrooms have Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices

There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the building, mounted on Notifier B710LPA low-profile bases.

The air handling units mostly have Notifier FSD-751PLA addressable photoelectric smoke detectors, and a couple have System Sensor D1420A conventional photoelectric 4-wire duct smoke detectors, wired to Notifier FMM-101A modules.

Modules

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system flow switches.

[[]