| FACP: Notifier AFP-200 <br /> FACP Location: Side Entrance<br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2010s <br />Year Opened: 1950s | | FACP: Notifier AFP-200 <br /> FACP Location: Side Entrance<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Continuous <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2010s <br />Year Opened: 1950s | ||
|} | |} | ||
The '''Crossroads Market''' is a large indoor farmer’s market located at 1235 26 Avenue Southeast, in Calgary, Alberta, Canada. The market opened in the 1950s, and the fire alarm system was upgraded in 1995. | The '''Crossroads Market''' is a large indoor farmer’s market located at 1235 26 Avenue Southeast, in Calgary, Alberta, Canada. The market opened in the 1950s, and the fire alarm system was upgraded in 1995. | ||
Line 17: | Line 17: | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
Most pull stations are Notifier NFM-950B conventional single-action pull stations. Some areas have Notifier MPS-950B conventional single-action pull stations as deficiency replacements. All NFM-series stations are wired to Notifier MMX-101A addressable monitor modules, and all MPS-series stations are wired to Notifier FMM-101A addressable monitor modules. All modules are located directly behind each station. | Most pull stations are Notifier NFM-950B conventional single-action pull stations. | ||
Some areas have Notifier MPS-950B conventional single-action pull stations as deficiency replacements. | |||
All NFM-series stations are wired to Notifier MMX-101A addressable monitor modules, and all MPS-series stations are wired to Notifier FMM-101A addressable monitor modules. All modules are located directly behind each station. | |||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
None noticed. | None noticed. | ||
==== Modules ==== | |||
There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches. | |||
==== EOLs ==== | |||
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits. | |||
[[Category:Calgary]] | [[Category:Calgary]] |
Latest revision as of 09:59, 24 September 2024
System Specifications |
---|
FACP: Notifier AFP-200 FACP Location: Side Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2010s Year Opened: 1950s |
The Crossroads Market is a large indoor farmer’s market located at 1235 26 Avenue Southeast, in Calgary, Alberta, Canada. The market opened in the 1950s, and the fire alarm system was upgraded in 1995.
System Specifications (1995-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier AFP-200 addressable fire alarm system. The panel is located in the side entrance vestibule. The system runs Notifier’s CLIP addressable protocol, and the system coding is continuous.
Annunciators[edit | edit source]
There is a Notifier LCD-80 annunciator near the main entrance.
Notification Appliances[edit | edit source]
All notification appliances are System Sensor “Multi-Alert” MASS24LOA sounder/strobes (red, wall-mount, tone setting unknown).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
Most pull stations are Notifier NFM-950B conventional single-action pull stations.
Some areas have Notifier MPS-950B conventional single-action pull stations as deficiency replacements.
All NFM-series stations are wired to Notifier MMX-101A addressable monitor modules, and all MPS-series stations are wired to Notifier FMM-101A addressable monitor modules. All modules are located directly behind each station.
Automatic Detection Devices[edit | edit source]
None noticed.
Modules[edit | edit source]
There are Notifier MMX-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.