| FACP: Edwards EST3<br /> FACP Location: Unknown <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, | | FACP: Edwards EST3<br /> FACP Location: Unknown <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, Genesis<br />Date of last known Upgrade: 2020 <br />Year Opened: 2010 | ||
|} | |} | ||
The '''Beaumont Sport and Recreation Centre''' is a recreation centre located at 5001 Rue Eaglemont, in Beaumont, Alberta, Canada. The building houses a field house, a large aquatic centre, a fitness centre, and several arenas. The building opened in 2010 as the AquaFit Centre, and was extensively expanded in 2020. The fire alarm system was installed following the expansion. | The '''Beaumont Sport and Recreation Centre''' is a recreation centre located at 5001 Rue Eaglemont, in Beaumont, Alberta, Canada. The building houses a field house, a large aquatic centre, a fitness centre, and several arenas. The building opened in 2010 as the AquaFit Centre, and was extensively expanded in 2020. The fire alarm system was installed following the expansion. | ||
Line 16: | Line 16: | ||
All indoor notification appliances are Edwards "Genesis" G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). The ones in the pool area are original. | All indoor notification appliances are Edwards "Genesis" G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). The ones in the pool area are original. | ||
For exterior notification, there is an Edwards CS405-8A-T (red, 110cd) weatherproof remote strobe near the entrance. | |||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== |
Latest revision as of 00:45, 17 November 2024
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2020 Year Opened: 2010 |
The Beaumont Sport and Recreation Centre is a recreation centre located at 5001 Rue Eaglemont, in Beaumont, Alberta, Canada. The building houses a field house, a large aquatic centre, a fitness centre, and several arenas. The building opened in 2010 as the AquaFit Centre, and was extensively expanded in 2020. The fire alarm system was installed following the expansion.
System Specifications (2020-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs EST's Signature addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There is an Edwards EST 3-10ANN 10-base position LCD annunciator in the main entrance vestibule.
Notification Appliances[edit | edit source]
All indoor notification appliances are Edwards "Genesis" G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd). The ones in the pool area are original.
For exterior notification, there is an Edwards CS405-8A-T (red, 110cd) weatherproof remote strobe near the entrance.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are EST SIGA-270 addressable single-action pull stations. The ones in the pool area are original.
Automatic Detection Devices[edit | edit source]
There are Edwards SIGA-PD addressable photoelectric smoke detectors in some areas, mounted on SIGA-SB bases.
There are Edwards SIGA-SD addressable photoelectric duct smoke detectors on the air handling units, indicated by SIGA-LED LED indicators.
There is also a wet sprinkler system with waterflow detection protecting the facility.
Modules[edit | edit source]
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-IM addressable isolator modules on the SLC.
EOLs[edit | edit source]
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.
Former System Specifications (2010-2020)[edit | edit source]
Former System Specifications |
---|
FACP: EST QuickStart QS4 FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, EST Date of last known Upgrade: N/A Year Decomissioned: 2019 |
FACP[edit | edit source]
The building was protected by an EST QuickStart QS4 addressable fire alarm system. The panel location was unknown. The system runs EST’s Signature addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There was an EST-SRA4 LCD annunciator at the main entrance.
Notification Appliances[edit | edit source]
All notification appliances were Edwards “Genesis” G1-HDVM horn/strobes (white, wall-mount, no lettering, set to 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on EST SIGA-SB bases. There is also a wet sprinkler system with waterflow detection protecting the entire facility.
Modules[edit | edit source]
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There were Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.