(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Mircom FleX-Net <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, Mircom <br />Date of last known Upgrade: N/A <br />Year Opened: 2022 |} '''Sierra Greens''' is an apartment complex owned and operated by Broadstreet Propertie...") |
No edit summary |
||
Line 22: | Line 22: | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Mircom MIX-4010 addressable photoelectric smoke detectors throughout all common areas, mounted on Mircom MIX-4002 bases. <br>There is a Mircom D2A conventional photoelectric duct smoke detector on the main air handling unit, wired to a Mircom MIX-4040 addressable monitor module. | There are Mircom MIX-4010 addressable photoelectric smoke detectors throughout all common areas, mounted on Mircom MIX-4002 bases. <br>There is a Mircom "InnovairFlex" D2A conventional photoelectric duct smoke detector on the main air handling unit, wired to a Mircom MIX-4040 addressable monitor module. | ||
====Modules==== | ====Modules==== |
Latest revision as of 15:42, 11 January 2025
System Specifications |
---|
FACP: Mircom FleX-Net FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Mircom Date of last known Upgrade: N/A Year Opened: 2022 |
Sierra Greens is an apartment complex owned and operated by Broadstreet Properties. This page will cover Building 21805, located at 21805 91A Ave NW, in Edmonton, Alberta, Canada. The building was built in 2022, and the fire alarm system is original.
System Specifications[edit | edit source]
FACP[edit | edit source]
The building is protected by a Mircom FleX-Net addressable fire alarm system. This is a single-node system; the panel is located in the main entrance vestibule. The system runs Mircom’s MGC addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All common areas have Mircom FHS-400-RR horn/strobes (red, wall-mount, set to 15cd).
Each suite has a Mircom FS-400-WW remote strobe (white, wall-mount, set to 15cd) in the main living area, and Mircom MH-S25WA silenceable mini-horns (white) in each bedroom.
For outdoor notification, there is a System Sensor “SpectrAlert Advance” P2RKA weatherproof horn/strobe (red, wall-mount) outside the main entrance.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Mircom MS-401MP addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Mircom MIX-4010 addressable photoelectric smoke detectors throughout all common areas, mounted on Mircom MIX-4002 bases.
There is a Mircom "InnovairFlex" D2A conventional photoelectric duct smoke detector on the main air handling unit, wired to a Mircom MIX-4040 addressable monitor module.
Modules[edit | edit source]
There are Mircom MIX-4040 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Mircom MIX-4045 addressable relay modules for elevator recall.
There are Mircom MIX-4070 isolator modules on the SLC.
EOLs[edit | edit source]
There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.