More actions
No edit summary |
No edit summary |
||
| Line 7: | Line 7: | ||
| FACP: Grinnell Series M-1000 <br />FACP Location: West Building, Cedar Suites Entrance<br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal (self-coded) <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2022 <br />Year Opened: 1972 | | FACP: Grinnell Series M-1000 <br />FACP Location: West Building, Cedar Suites Entrance<br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal (self-coded) <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2022 <br />Year Opened: 1972 | ||
|} | |} | ||
'''Jasper Inn & Suites''' is a 3-star hotel located at 98 Geikie St, Jasper, AB. It features an indoor pool, many suites and spans two floors | '''Jasper Inn & Suites''' is a 3-star hotel located at 98 Geikie St, Jasper, AB. It features an indoor pool, many suites and spans two floors. | ||
Three buildings have systems: the main office/Cedar Suites building and the Inn Grill/pool building, both built in 1972 share the | Three of the four buildings have fire alarm systems: the main office/Cedar Suites building and the Inn Grill/pool building, both built in 1972 share a system, with minor upgrades in the mid-1980s. Maligne Suites, built around 1990, is protected by its own fire alarm system. Both fire alarm systems underwent panel upgrades in the early 2000s, and notification appliance upgrades in 2020. The pull stations in Maligne Suites and most of the main building are original. | ||
Both fire alarm systems underwent panel upgrades in the 2000s, and | |||
==System Specifications (Cedar Suites & Main Building) (2000s-present) == | ==System Specifications (Cedar Suites & Main Building) (2000s-present) == | ||
====FACP==== | ====FACP==== | ||
The buildings are protected by a Grinnell Series M-1000 conventional fire alarm system. The panel is located in the Cedar Suites entrance vestibule in the west building, adjacent to reception | The buildings are protected by a Grinnell Series M-1000 conventional fire alarm system. The panel is located in the Cedar Suites entrance vestibule in the west building, adjacent to reception. The system coding is temporal. | ||
The Series M-1000 replaced an Edwards Custom 6500 in the 2000s, and is in one of the cabinets. There were formerly two separate 6500's supervising each building. After the upgrade, they were wired into one panel. The other cabinet is now covered, which was used for the main building. | The Series M-1000 replaced an Edwards Custom 6500 in the 2000s, and is in one of the cabinets. There were formerly two separate 6500's supervising each building. After the upgrade, they were wired into one panel. The other cabinet is now covered, which was used for the main building. | ||
| Line 47: | Line 45: | ||
| | | | ||
|- | |- | ||
| FACP: Mircom Series FA-1000 <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes <br />Date of last known Upgrade: 2022 <br />Year Opened: | | FACP: Mircom Series FA-1000 <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes <br />Date of last known Upgrade: 2022 <br />Year Opened: Circa 1990 | ||
|} | |} | ||
====FACP==== | ====FACP==== | ||
Revision as of 20:54, 21 February 2025
| System Specifications |
|---|
| FACP: Grinnell Series M-1000 FACP Location: West Building, Cedar Suites Entrance System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal (self-coded) Strobes Synchronized: No Date of last known Upgrade: 2022 Year Opened: 1972 |
Jasper Inn & Suites is a 3-star hotel located at 98 Geikie St, Jasper, AB. It features an indoor pool, many suites and spans two floors.
Three of the four buildings have fire alarm systems: the main office/Cedar Suites building and the Inn Grill/pool building, both built in 1972 share a system, with minor upgrades in the mid-1980s. Maligne Suites, built around 1990, is protected by its own fire alarm system. Both fire alarm systems underwent panel upgrades in the early 2000s, and notification appliance upgrades in 2020. The pull stations in Maligne Suites and most of the main building are original.
System Specifications (Cedar Suites & Main Building) (2000s-present)
FACP
The buildings are protected by a Grinnell Series M-1000 conventional fire alarm system. The panel is located in the Cedar Suites entrance vestibule in the west building, adjacent to reception. The system coding is temporal.
The Series M-1000 replaced an Edwards Custom 6500 in the 2000s, and is in one of the cabinets. There were formerly two separate 6500's supervising each building. After the upgrade, they were wired into one panel. The other cabinet is now covered, which was used for the main building.
Notification Appliances
Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd), except for above the panel and the south hotel hallways of the main building.
The south hallways in the main building have System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd), likely new old stock.
Above the panel in the stairwell, there is a System Sensor PA400SRA mini-horn (red, silenceable) with a System Sensor SS-24 remote strobe beside it (red, wall-mount, 1.5cd), the only notification appliances to remain untouched after the upgrade; these were installed to indicate that the main building was in alarm when there were two separate panels. These are now wired to the one panel, and will go off during any alarm.
The P2RA's and P2RLA's were installed in 2020, replacing Edwards 439D-6AWC vibrating bells (6" gong, 1986) and some Edwards "Durabel" 6100D vibrating bells (6" gong, original).
Initiating Devices
Pull Stations
All pull stations are Edwards 270-SPO conventional single-action pull stations. Most are original in the main building, and there are some installed in 1986. The west building's 270-SPO's were all installed around 1986.
Automatic Detection Devices
Most smoke detectors are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors, located throughout both buildings. The one by the panel was installed as a deficiency replacement for a System Sensor 1400A conventional ionization smoke detector in 2022.
The laundry hallway and ski locker hallway both contain System Sensor 5601A conventional 135°F fixed-temperature/rate of rise mechanical heat detectors.
The pool hallway contains one Mircom TD-135 conventional 135°F fixed-temperature heat detector.
These replaced Edwards 281C fixed/rate-of-rise heat detectors after a recall.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all circuits.
System Specifications (Maligne Suites) (2000s-present)
| System Specifications |
|---|
| FACP: Mircom Series FA-1000 FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes Date of last known Upgrade: 2022 Year Opened: Circa 1990 |
FACP
This building is protected by a Mircom Series FA-1000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous, as the notification appliances are self-coded to temporal.
The Series 1000 replaced a Notifier System 500 in the late 2000s.
Notification Appliances
All notification appliances are System Sensor “L-Series” P2RLA-E horn/strobes (red, wall-mount, English only, set to 15cd).
These were installed in 2020 replacing Notifier KMS-6-24VDC/P motor bells (6” gong).
Initiating Devices
Pull Stations
All pull stations are Notifier FM950-B conventional pull stations. These are the original models, with the black labels.
Automatic Detection Devices
The smoke detectors are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all circuits.