The '''Lake Bonavista Community Association''' is a small recreation centre in Lake Bonavista, SE Calgary. It was built in 1970, but does not have the original fire alarm system. Almost all of the fire bells and most pull stations are original to the building! | The '''Lake Bonavista Community Association''' is a small recreation centre in Lake Bonavista, SE Calgary. It was built in 1970, but does not have the original fire alarm system. Almost all of the fire bells and most pull stations are original to the building! | ||
== System Specifications == | == System Specifications == | ||
==== FACP ==== | ==== FACP ==== | ||
The fire alarm control panel is a Mircom FA-1000. There's an annunciator at the entrance, but the main panel is located in the facility manager's office. The FA-1000 replaced an Edwards Custom 6500 in 2006. The "SIGNAL SILENCE" button has the writing "Bell" above it, as well as the NACs saying "bells" | |||
The fire alarm control panel is a Mircom FA-1000. There's an annunciator at the entrance, but the main panel is located in the facility manager's office. The FA-1000 | |||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
Most of the notification appliances consist of the original Edwards "Durabel" 6100D (6" gong) vibrating bells from the 1964 era. Some Durabels have been replaced with newer variants (late 1970s-1990 logo, or 1990s logo). In the gymnasium and the entrance, there are Simplex 2901-9723 motor bells replacing failed Edwards bells. There is also a painted-over Edwards 881-D flush mount horn in the dressing room hallway, however it is unknown if it is still in use. | |||
Most of the notification appliances consist of the original Edwards "Durabel" 6100D (6" gong) vibrating bells from the 1964 era. Some Durabels have been replaced with newer variants (late 1970s-1990 logo, or 1990s logo). In the gymnasium and the entrance, there are Simplex 2901-9723 motor bells replacing failed Edwards bells. | |||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
Most of the pull stations consist of the original Edwards 270-SPO with the square shield E logo. Replacement pull stations include a Notifier MPS-950B in the smaller arena, and a newer Mircom MS-401 at one entrance. | Most of the pull stations consist of the original Edwards 270-SPO with the square shield E logo. Replacement pull stations include a Notifier MPS-950B in the smaller arena, and a newer Mircom MS-401 at one entrance. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
None noticed. | None noticed. |
Revision as of 11:09, 10 June 2021
System Specifications |
---|
FACP: Mircom FA-1000 System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR Date of last known Upgrade: Mid-late 2010s Year Opened: 1970 |
The Lake Bonavista Community Association is a small recreation centre in Lake Bonavista, SE Calgary. It was built in 1970, but does not have the original fire alarm system. Almost all of the fire bells and most pull stations are original to the building!
System Specifications
FACP
The fire alarm control panel is a Mircom FA-1000. There's an annunciator at the entrance, but the main panel is located in the facility manager's office. The FA-1000 replaced an Edwards Custom 6500 in 2006. The "SIGNAL SILENCE" button has the writing "Bell" above it, as well as the NACs saying "bells"
Notification Appliances
Most of the notification appliances consist of the original Edwards "Durabel" 6100D (6" gong) vibrating bells from the 1964 era. Some Durabels have been replaced with newer variants (late 1970s-1990 logo, or 1990s logo). In the gymnasium and the entrance, there are Simplex 2901-9723 motor bells replacing failed Edwards bells. There is also a painted-over Edwards 881-D flush mount horn in the dressing room hallway, however it is unknown if it is still in use.
Initiating Devices
Pull Stations
Most of the pull stations consist of the original Edwards 270-SPO with the square shield E logo. Replacement pull stations include a Notifier MPS-950B in the smaller arena, and a newer Mircom MS-401 at one entrance.
Automatic Detection Devices
None noticed.