More actions
(Rare to see a Costco with Notifier. Or even anything but Fire-Lite.) |
(There was a t in the panel model. Stupid T. Get out of there.) |
||
Line 1: | Line 1: | ||
‘’’Costco’’’ is a chain of big-box warehouse stores across North America. | ‘’’Costco’’’ is a chain of big-box warehouse stores across North America. This particular store is located in the East Fairview Industrial area of Southeast Calgary. It was built in 2006, but the system is not original. | ||
==System Specifications== | ==System Specifications== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a | The building is protected by a Notifier NotiFireNet networked fire alarm system. There are two panels, both are NFS-320C addressable fire alarm panels. These panels were installed in the 2010s, and likely replaced AFP-200 panels. The system does code 3 in alarm. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All notification appliances are System Sensor “SpectrAlert” P1224MCA horn/strobes, set on 75 candela. | All notification appliances are System Sensor “SpectrAlert” P1224MCA horn/strobes, set on 75 candela. These are set on electromechanical code 3. | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Notifier MPS-950B conventional “tab” pull stations. | All pull stations are Notifier MPS-950B conventional “tab” pull stations. As they are conventional, they have Notifier FMM-101A addressable modules attached to them. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
The building is protected by a sprinkler system with waterflow detection, so there are no detectors. | The building is protected by a sprinkler system with waterflow detection, so there are no detectors. |
Revision as of 13:57, 8 November 2021
‘’’Costco’’’ is a chain of big-box warehouse stores across North America. This particular store is located in the East Fairview Industrial area of Southeast Calgary. It was built in 2006, but the system is not original.
System Specifications
FACP
The building is protected by a Notifier NotiFireNet networked fire alarm system. There are two panels, both are NFS-320C addressable fire alarm panels. These panels were installed in the 2010s, and likely replaced AFP-200 panels. The system does code 3 in alarm.
Notification Appliances
All notification appliances are System Sensor “SpectrAlert” P1224MCA horn/strobes, set on 75 candela. These are set on electromechanical code 3.
Initiating Devices
Pull Stations
All pull stations are Notifier MPS-950B conventional “tab” pull stations. As they are conventional, they have Notifier FMM-101A addressable modules attached to them.
Automatic Detection Devices
The building is protected by a sprinkler system with waterflow detection, so there are no detectors.