==== FACP ==== | ==== FACP ==== | ||
The hotel is protected by an Edwards 6616 fire alarm system. The panel is located in the main entrance, and was installed in 1989, confirmed by the date code on the heat detectors, as well as the cabinet style. The panel has 3 zones in use. As of August 29, 2021 the panel is in alarm for all zones in use plus one unused zone, and has the alarm silenced though the LED on the right side is on "RESET", which indicates a | The hotel is protected by an Edwards 6616 fire alarm system. The panel is located in the main entrance, and was installed in 1989, confirmed by the date code on the heat detectors, as well as the cabinet style. The panel has 3 zones in use. As of August 29, 2021 the panel is in alarm for all zones in use plus one unused zone, and has the alarm silenced though the LED on the right side is on "RESET", which indicates a main board failure. Therefore, the system is inoperable. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== |
Revision as of 19:57, 21 November 2021
System Specifications |
---|
FACP: Edwards 6616 System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR Date of last known Upgrade: 1989 Year Built: 1978 |
Raven Meadows Golf Resort is a golf resort located in Alder Flats, AB. The resort has an 18-hole golf course, an RV park with 42 sites, and a 2-story hotel with a restaurant in it. The golf resort opened in 1978, but the hotel's fire alarm system is not original. The fire alarm system also has some issues. The system has not been looked after for years, and was last inspected on August 4, 2006 by Abendroth Electric, who are now out of business.
System Specifications
FACP
The hotel is protected by an Edwards 6616 fire alarm system. The panel is located in the main entrance, and was installed in 1989, confirmed by the date code on the heat detectors, as well as the cabinet style. The panel has 3 zones in use. As of August 29, 2021 the panel is in alarm for all zones in use plus one unused zone, and has the alarm silenced though the LED on the right side is on "RESET", which indicates a main board failure. Therefore, the system is inoperable.
Notification Appliances
The notification appliances are an Edwards 439D-10AWC vibrating bell with its stickers peeled off in the hallway by the golf store and lounge, and a VERY rare silver Edwards "Durabel" 6100D (10" gong) vibrating bell in the hallway to the restaurant. Both seemed to be installed in 1989. It is unknown what is on the 2nd floor, as the main floor was only checked.
Initiating Devices
Pull Stations
The pull stations mostly consist of Edwards 275-C111 pull stations, which were likely installed when the 6616 was. There is a 2nd-generation Edwards 270-SPO (classic shield, no FIRE ALARM) near the Durabel, and is likely the only original device to the building.
Automatic Detection Devices
There are Edwards 281C fixed temperature/rate of rise heat detectors installed throughout the hotel, and were all installed in 1989, confirmed by the date code label on the side.