Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Centennial Planetarium: Difference between revisions

From FireAlarmPedia
m (Simplex NimrodES moved page Contemporary Calgary to Centennial Planetarium without leaving a redirect: real building name)
(Revamped page. Piece of shit system, Nathan please update! Also why two systems in one building??)
Line 1: Line 1:
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 6: Line 5:
|  
|  
|-
|-
| FACP: EST3 <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: 2018 <br />Year Opened: 1967
| FACP: Edwards EST3X <br /> FACP Location: TBA <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2019 <br />Year Opened: 1967
|}'''Contemporary Calgary''' is an art museum in Calgary. It is in Downtown Calgary, off of 11 St SW. It was where the former Telus World Of Science in Calgary was before 2011. The building is from 1967, but the alarm system is from around 2018. Following the opening of [[TELUS Spark]] in 2011, Telus World of Science closed its doors. Prior to then, the space had two fire alarm systems, one Notifier and one EST.
|}
 
 
'''Centennial Planetarium''' was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of [[TELUS Spark]] in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant.
== System Specifications (2018-present) ==
== System Specifications (2018-present) ==
==== FACP ====
==== FACP ====
The fire alarm panel is most likely an EST3. It was installed in 2018. It is unknown if the system is two-stage.  
The planetarium is protected by an Edwards EST3X addressable fire alarm system. The panel is located (Nathan, please fill). The system runs EST's Signature-series addressable protocol, and the system coding is Temporal.
==== Notification Appliances ====
==== Notification Appliances ====
The notification appliances are EST "Genesis" G1R-HDVM (red, wall, no FIRE) horn/strobes, seen throughout.
The notification appliances are EST "Genesis" G1R-HDVM (red, wall, no FIRE) horn/strobes throughout the building. There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations are either EST SIGA-270 or SIGA-270P.
The pull stations are EST SIGA-270 addressable pull stations.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
The smoke detectors are most likely EST SIGA2-PS.
The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases.
== Former System Specifications (Notifier TWOS) (2000s-2011) ==
== Former System Specifications (East Wing) (2000s-2011) ==
==== FACP ====
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 26: Line 27:
|  
|  
|-
|-
| FACP: Notifier AFP1010 <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: 2000s <br /> Year Decommissioned: 2011
| FACP: Notifier AFP-400 <br /> FACP Location: Unknown <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (first stage) <br> Temporal (GA) <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2005 <br />Year Decomissioned: 2011
|}
|}
The fire alarm panel was a Notifier AFP1010. It was wired to an EST 6632 or EST2. Both systems were wired to trip each other.  
==== FACP ====
The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The system coding was 20BPM for first stage, and temporal for general alarm.
==== Notification Appliances ====
==== Notification Appliances ====
For the Notifier part, the notification appliances were Notifier KMS-10-24A motor bells on Wheelock RSSP-2415W-FR strobe plates.
The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd)
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations were Notifier NFM-950B.
The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier MMX-101A addressable modules, behind each station.
== Former System Specifcations (EST for TWOS) (Early 2000s-2011) ==
 
==== FACP ====
==== Automatic Detection Devices ====
 
Not available
== Former System Specifcations (West Wing) (Early 2000s-2011) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 42: Line 47:
|  
|  
|-
|-
| FACP: Unknown panel by EST <br />System Type: Conventional or Addressable (Hybrid) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC or 24VFWR <br />Date of last known Upgrade: Early 2000s <br /> Year Decommissioned: 2011
| FACP: EST2? <br /> FACP Location: Unknown <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (first stage) <br> Continuous (GA) <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2000s <br />Year Decomissioned: 2011
|}
|}
The fire alarm control panel for the Edwards part was likely an EST3, EST2 or EST 6632. It was wired into the Notifier AFP1010.
 
==== FACP ====
 
The West Wing was most likely protected by an EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm.
==== Notification Appliances ====
==== Notification Appliances ====
The notification appliances were Edwards 439D-6AWC vibrating bells on EST 403-5A-R "Integrity" strobe plates. Some were not seen with strobe plates.
The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd).  
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations for the EST part were Edwards 270-SPO.
The pull stations were all Edwards 270P-SPO conventional two-stage pull stations.
 
==== Automatic Detection Devices ====
 
Not available.
[[Category:Facilities]]
[[Category:Facilities]]

Revision as of 23:34, 12 November 2022

System Specifications
FACP: Edwards EST3X
FACP Location: TBA
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2019
Year Opened: 1967


Centennial Planetarium was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of TELUS Spark in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant.

System Specifications (2018-present)

FACP

The planetarium is protected by an Edwards EST3X addressable fire alarm system. The panel is located (Nathan, please fill). The system runs EST's Signature-series addressable protocol, and the system coding is Temporal.

Notification Appliances

The notification appliances are EST "Genesis" G1R-HDVM (red, wall, no FIRE) horn/strobes throughout the building. There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected.

Initiating Devices

Pull Stations

The pull stations are EST SIGA-270 addressable pull stations.

Automatic Detection Devices

The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases.

Former System Specifications (East Wing) (2000s-2011)

System Specifications
FACP: Notifier AFP-400
FACP Location: Unknown
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (first stage)
Temporal (GA)
Strobes Synchronized: No
Date of last known Upgrade: 2005
Year Decomissioned: 2011

FACP

The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The system coding was 20BPM for first stage, and temporal for general alarm.

Notification Appliances

The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd)

Initiating Devices

Pull Stations

The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier MMX-101A addressable modules, behind each station.

Automatic Detection Devices

Not available

Former System Specifcations (West Wing) (Early 2000s-2011)

System Specifications
FACP: EST2?
FACP Location: Unknown
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (first stage)
Continuous (GA)
Strobes Synchronized: Yes
Date of last known Upgrade: 2000s
Year Decomissioned: 2011

FACP

The West Wing was most likely protected by an EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm.

Notification Appliances

The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd).

Initiating Devices

Pull Stations

The pull stations were all Edwards 270P-SPO conventional two-stage pull stations.

Automatic Detection Devices

Not available.