| FACP: Vigilant VS2<br />System Type:Addressable (Hybrid Manner)<br /> System Line Voltage: 120VAC<br />NAC Voltage:24VFWR<br />Date of last known Upgrade: 2014<br />Year Opened: 1955 <br> 1993 (as Holy Spirit)
| FACP: Vigilant VS2 <br /> FACP Location: Main Entrance Vestibule <br />System Type: Hybrid <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: late 2010s <br />Year Opened: 1955/1993
|}
|}
'''Holy Spirit School''' is a catholic elementary school in Downtown Cochrane, AB. The school was built in the 1955 as Andrew Sibbald School. The school then underwent renovations in 1959, 1969 and 1989. The school went yet another renovation and started to be rented by CCSD in 1993, in which the school became Holy Spirit. The school has had two fire alarm systems in the past 28 years of operation, and there are two old, possibly original pull stations still intact. The current fire alarm system has been in the school since 2014. In June 2021, a new school is going to be constructed to replace Holy Spirit. The system is serviced and managed by Altex Security Systems.
 
'''129 Powell Street''' is a the address given to an abandoned school building in Downtown Cochrane, AB. The school was built in the 1955 as Andrew Sibbald School. The school then underwent renovations in 1959, 1969 and 1989. The school went yet another renovation and started to be rented by CCSD in 1993, in which the school became Holy Spirit. The school has had two fire alarm systems in the past 28 years of operation, and there are two old, possibly original pull stations still intact. The current fire alarm system has been in the school since 2014. In June 2021, a new school is going to be constructed to replace Holy Spirit. In 2022, the school moved. The system is serviced and managed by Altex Security Systems.
== System Specifications (2014-present) ==
== System Specifications (2014-present) ==
==== FACP ====
==== FACP ====
The fire alarm panel is a Vigilant VS2 (rebranded EST iO500) installed in June 2014. Although this panel is addressable, the system is not set up in an addressable manner, as it replaced an EST 6616 (see below for more info). The panel is located at the front entrance. All strobes on the system are synchronized, and all horns do code-3.  
The school is protected by a Vigilant VS2 hybrid-addressable fire alarm system. The panel is located in the main entrance vestibule, and was installed in June 2014 as a replacement for an EST 6616. The system partially ran Vigilant's GSA addressable protocol, and the system coding is temporal.
==== Notification Appliances ====
==== Notification Appliances ====
The notification appliances inside are all EST "Genesis" G1R-HDVM (red, wall, no FIRE lettering) horn/strobes. In the hallways, most are on these cool custom trim plates for two horn/strobes each, facing each end, though some are on regular trim plates. There are some surface mounted, for example, in three classrooms (one which was new for 2014), and in the "time-in room". There is also one installed in the library, and there are two in the gymnasium on trim plates. They are all set to 15 candela, but can vary between low and high volume. There is an EST "Genesis" GC-HDVM (white, ceiling, no FIRE lettering) horn/strobe in the new portable. For outdoor notification, there is an EST "Genesis" WG4RF-HVMC (red, FIRE lettering) horn/strobe pointed at the large field, under a protective cover. It is synchronized with the indoor horn/strobes as well. All of these horn/strobes were installed in 2014, replacing the bell/strobes.  
The notification appliances inside are all EST "Genesis" G1R-HDVM (red, wall, no FIRE lettering) horn/strobes, mostly installed on two-device backboxes in the hallway. They can also be found in three classrooms and the library. They are all set to 15 cd, but can vary between low and high volume. There is an EST "Genesis" GC-HDVM (white, ceiling, no FIRE lettering) horn/strobe in the new portable. For outdoor notification, there is an EST "Genesis" WG4RF-HVMC (red, FIRE lettering) horn/strobe pointed at the large field, under a protective cover. All of these horn/strobes were installed in 2014, replacing the bell/strobes.  
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations were kept from the previous system. They are all Edwards 270-SPO pull stations, mostly from 1993 when the 6616 was installed. However, there are two that are the first generation (classic shield, FIRE ALARM at top), installed in 1955, 1959 or 1969. One of which is located in the gymnasium and one is at the end of the school, near emergency exit and where the 6" bell/strobe was. By May 2022, a 270-SPO by the end of the school was replaced with a newer variant.
The pull stations are all Edwards 270-SPO conventional pull stations left over from the previous system. They were mostly installed in 1993 when the 6616 was installed, however there is one original first-generation 270-SPO (Classic shield, FIRE ALARM) in a portable. As of May 2022, a 270-SPO by the end of the school was replaced with a newer variant.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors installed in 2014. The heat detectors are Edwards EC20FTU-3 fixed temprature heat detectors. They were installed in 2020 replacing Edwards 281B-PL rate-of-rise heat detectors that were kept from the EST 6616 (installed 1993).  
The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors installed in 2014. The heat detectors are Edwards EC20FTU-3 fixed temprature heat detectors. They were installed in 2020 replacing Edwards 281B-PL rate-of-rise heat detectors that were kept from the EST 6616 (installed 1993).  
Line 25: Line 26:
|  
|  
|-
|-
| FACP: EST 6616 <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />Date of last known Upgrade: Early 2000s <br />Year Decommissioned: 2014
| FACP: EST 6616 <br /> FACP Location: Main Entrance Vestibule <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Continuous <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2000s <br />Year Decomissioned: 2014
|}
|}
==== FACP ====
==== FACP ====
The fire alarm panel was an EST 6616, which was installed in 1993. Only eight zones were in use at the time. The system was set to continuous. It was replaced in 2014 with the Vigilant system, although nothing was wrong.
The school was protected by an EST 6616 conventional fire alarm system. The panel was located in the main entrance vestibule, and was installed in 1993. Only eight zones were in use at the time. The system coding was continuous. It was replaced in 2014 with the Vigilant system despite no issues.
==== Notification Appliances ====
==== Notification Appliances ====
The main indoor notification appliances were Wheelock MBS-G10-24 motor bell/strobes. They were only in the hallways and the gymnasium. A couple Wheelock bell/strobes broke down over the years, and the one by the kindergarten classroom and under a water fountain was replaced with an Edwards 439D-10AWC vibrating bell on an EST 403-5A-R Integrity strobe plate in the early 2000s. The bell/strobe at the end of the school and by the old 270-SPO was replaced with an Edwards 439D-6AWC vibrating bell on a Simplex 4903-9101 strobe plate with the strobe above the bell. The outdoor notification appliances were Edwards 439D-10AWC vibrating bells, one by the large field and one by the grade 1 entrance. Unlike the indoor 439Ds, these ones were installed in 1993. For some reason, the bells were not loud enough, and when they removed the outdoor bells, they only replaced one.
Most notification appliances were Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5cd). There was an Edwards 439D-10AWC vibrating bell (10" gong) on an EST "Integrity" 403-5A-R (15cd) strobe plate installed in the early 2000s as a deficiency replacement. There was an Edwards 439D-6AWC vibrating bell (6" gong) on a Simplex 4903-9101 strobe plate (4.5cd) with the strobe above the bell in the portable. The outdoor notification appliances were Edwards 439D-10AWC vibrating bells (10" gong), one by the large field and one by an entrance, installed in 1993. For some reason, the bells were not loud enough, and when they removed the outdoor bells, they only replaced one.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations were the Edwards 270-SPO pull stations that are still installed today.
The pull stations were the Edwards 270-SPO pull stations that are still installed today.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
The heat detectors were the Edwards 280B-PL that are still installed, but the smoke detectors were Edwards 6264B ionization smoke detectors. One was replaced with an EST SIGA2-PS in 2014 before the Vigilant system was installed.
The heat detectors were the Edwards 280B-PL that were kept on the Vigilant system, but the smoke detectors were Edwards 6249C photoelectric smoke detectors.  
[[Category:Facilities]]
[[Category:Facilities]]

Revision as of 23:44, 12 November 2022

System Specifications
FACP: Vigilant VS2
FACP Location: Main Entrance Vestibule
System Type: Hybrid
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: late 2010s
Year Opened: 1955/1993

129 Powell Street is a the address given to an abandoned school building in Downtown Cochrane, AB. The school was built in the 1955 as Andrew Sibbald School. The school then underwent renovations in 1959, 1969 and 1989. The school went yet another renovation and started to be rented by CCSD in 1993, in which the school became Holy Spirit. The school has had two fire alarm systems in the past 28 years of operation, and there are two old, possibly original pull stations still intact. The current fire alarm system has been in the school since 2014. In June 2021, a new school is going to be constructed to replace Holy Spirit. In 2022, the school moved. The system is serviced and managed by Altex Security Systems.

System Specifications (2014-present)

FACP

The school is protected by a Vigilant VS2 hybrid-addressable fire alarm system. The panel is located in the main entrance vestibule, and was installed in June 2014 as a replacement for an EST 6616. The system partially ran Vigilant's GSA addressable protocol, and the system coding is temporal.

Notification Appliances

The notification appliances inside are all EST "Genesis" G1R-HDVM (red, wall, no FIRE lettering) horn/strobes, mostly installed on two-device backboxes in the hallway. They can also be found in three classrooms and the library. They are all set to 15 cd, but can vary between low and high volume. There is an EST "Genesis" GC-HDVM (white, ceiling, no FIRE lettering) horn/strobe in the new portable. For outdoor notification, there is an EST "Genesis" WG4RF-HVMC (red, FIRE lettering) horn/strobe pointed at the large field, under a protective cover. All of these horn/strobes were installed in 2014, replacing the bell/strobes.

Initiating Devices

Pull Stations

The pull stations are all Edwards 270-SPO conventional pull stations left over from the previous system. They were mostly installed in 1993 when the 6616 was installed, however there is one original first-generation 270-SPO (Classic shield, FIRE ALARM) in a portable. As of May 2022, a 270-SPO by the end of the school was replaced with a newer variant.

Automatic Detection Devices

The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors installed in 2014. The heat detectors are Edwards EC20FTU-3 fixed temprature heat detectors. They were installed in 2020 replacing Edwards 281B-PL rate-of-rise heat detectors that were kept from the EST 6616 (installed 1993).

Former System Specifications (1993-2014)

System Specifications
FACP: EST 6616
FACP Location: Main Entrance Vestibule
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: 2000s
Year Decomissioned: 2014

FACP

The school was protected by an EST 6616 conventional fire alarm system. The panel was located in the main entrance vestibule, and was installed in 1993. Only eight zones were in use at the time. The system coding was continuous. It was replaced in 2014 with the Vigilant system despite no issues.

Notification Appliances

Most notification appliances were Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5cd). There was an Edwards 439D-10AWC vibrating bell (10" gong) on an EST "Integrity" 403-5A-R (15cd) strobe plate installed in the early 2000s as a deficiency replacement. There was an Edwards 439D-6AWC vibrating bell (6" gong) on a Simplex 4903-9101 strobe plate (4.5cd) with the strobe above the bell in the portable. The outdoor notification appliances were Edwards 439D-10AWC vibrating bells (10" gong), one by the large field and one by an entrance, installed in 1993. For some reason, the bells were not loud enough, and when they removed the outdoor bells, they only replaced one.

Initiating Devices

Pull Stations

The pull stations were the Edwards 270-SPO pull stations that are still installed today.

Automatic Detection Devices

The heat detectors were the Edwards 280B-PL that were kept on the Vigilant system, but the smoke detectors were Edwards 6249C photoelectric smoke detectors.