Scotiabank Theatre Chinook: Difference between revisions

From FireAlarmPedia
mNo edit summary
(easy overhaul. terrible system. copied from Drive.)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: EST3X<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage:24VDC <br />Date of last known Upgrade: 2018 <br />Year Opened: 2001
| FACP: Edwards EST3X <br /> FACP Location: Main Lobby by Escalators <br />System Type: Addressable, Two-Stage <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (First Stage) <br> Temporal (GA) <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2017 <br />Year Opened: 2001
|}
|}
'''Scotiabank Theatre Chinook''' is a movie theater located in [[CF Chinook Centre]]. It opened as Paramount Chinook in 2001, and renamed Scotiabank Theatre Chinook in 2008 after Cineplex bought the chain. It has one IMAX screen, 16 screens, and an arcade, as well as the laser show that occurs every half hour. The fire alarm panel isn't original, but everything else is.


== System Specifications ==
‘’’Scotiabank Theatre''' is a theatre chain owned by Cineplex.  This particular theatre is located at 6455 Macleod Trail Southwest, in Calgary, Alberta, Canada.  The theatre is attached to [[CF Chinook Centre]], however the fire alarm systems are not connected.  The theatre opened in 2001, following the large expansion and renovation of the mall.  The fire alarm system is original with the exception of the FACP and smoke detectors.  The system is serviced by Guardian Electric.


==== FACP ====
==System Specifications==
====FACP====
The building is protected by an Edwards EST3X addressable fire alarm system.  The panel is located in the main lobby, to the left of the escalators.  The system runs EST’s Signature-series addressable protocol, and is configured for two-stage operation.  First stage coding is 20BPM, followed by temporal in general alarm.  This panel replaced an Edwards EST3, of which the cabinet remains, and is used as a junction box.


The fire alarm panel is an EST3X. It was installed in 2018, replacing the previous EST3. The EST3 cabinet still remains, but is gutted. The EST3X cabinet is about 10 feet from that cabinet. It is located by some escalators.
=====Annunciators=====
There is an Edwards EST3-LCDANN annunciator near the west entrance.


==== Notification Appliances ====
====Notification Appliances====
All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong) on EST 403-5A-R strobe plates (15cd).


The notification appliances are Edwards 439D-10AWC vibrating bells on EST "Integrity" 403-5A-R (15cd) strobe plates. They are all original from 2001.  
===Initiating Devices===
====Pull Stations====
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.


=== Initiating Devices ===
====Automatic Detection Devices====
 
There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.
==== Pull Stations ====
 
The pull stations are EST SIGA-270 addressable pull stations. They were installed when the EST3 was.
 
==== Automatic Detection Devices ====
 
None noticed.

Revision as of 21:47, 21 November 2022

System Specifications
FACP: Edwards EST3X
FACP Location: Main Lobby by Escalators
System Type: Addressable, Two-Stage
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (First Stage)
Temporal (GA)
Strobes Synchronized: Yes
Date of last known Upgrade: 2017
Year Opened: 2001

‘’’Scotiabank Theatre is a theatre chain owned by Cineplex. This particular theatre is located at 6455 Macleod Trail Southwest, in Calgary, Alberta, Canada. The theatre is attached to CF Chinook Centre, however the fire alarm systems are not connected. The theatre opened in 2001, following the large expansion and renovation of the mall. The fire alarm system is original with the exception of the FACP and smoke detectors. The system is serviced by Guardian Electric.

System Specifications

FACP

The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main lobby, to the left of the escalators. The system runs EST’s Signature-series addressable protocol, and is configured for two-stage operation. First stage coding is 20BPM, followed by temporal in general alarm. This panel replaced an Edwards EST3, of which the cabinet remains, and is used as a junction box.

Annunciators

There is an Edwards EST3-LCDANN annunciator near the west entrance.

Notification Appliances

All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong) on EST 403-5A-R strobe plates (15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.