There were Edwards 281B-PL fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time.
There were Edwards 281B-PL fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time.
[[Category:Facilities]]

Revision as of 16:07, 2 April 2023

System Specifications
FACP: Edwards 6616
FACP Location: Entrance Hallway
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Date of last known Upgrade: 1989
Year Opened: 1978
Year Decommissioned: 2021

Raven Meadows Golf Resort is a golf course located in Alder Flats, AB at 454065 Highway 22. Its amenities include a campground an 18-hole golf course, and formerly a hotel with a restaurant and pro shop. This page will cover the former hotel. The resort was opened in 1978, and the hotel underwent a system upgrade in 1989 confirmed by the heat detectors. As of August 2021, the system was not inspected in 15 years, the panel failed, and as a result was no longer able to detect fires. In October 2021, the hotel burnt down to the ground. The system was last serviced by Abendroth Electric in August 2006.

System Specifications

FACP

The hotel was protected by an Edwards 6616 conventional fire alarm system. The panel was located in the entrance hallway, and was installed in 1989. The system had three zones in use, and the system coding was continuous. As of August 2021, the panel was in alarm for all three zones plus one unused zone, and was set to “Normal” with the alarm silenced LED lit. This is a main board failure, and the system was no longer functional.

Notification Appliances

The notification appliances were mostly Edwards 439D-10AWC vibrating bells (10” gong). The one in the lobby was vandalized; both labels removed, and the gong was mounted on the striker with a crosshead screw instead of the original hex bolt. In the hallway to the restaurant, there was an Edwards “Durabel” 6100D (10” gong) vibrating bell, painted over with white except for the label. The bells were installed in 1989.

Initiating Devices

Pull Stations

Most pull stations except for one were Edwards 275-C111 conventional pull stations. These were installed with the 6616, and were located at every exit, including an awkward install by a sliding glass door pointed toward the door handle. There was one original Edwards 270-SPO in the restaurant hallway exit.

Automatic Detection Devices

There were Edwards 281B-PL fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time.