====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, and EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in some areas. All detectors were mounted on EST SIGA-SB bases. | There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, and EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in some areas. All detectors were mounted on EST SIGA-SB bases. | ||
[[Category: | [[Category:Facilitie] |
Revision as of 12:40, 3 April 2023
System Specifications |
---|
FACP: Notifier NFS2-3030C FACP Location: Basement Electrical Room System Type: (type) System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, SS Date of last known Upgrade: 2022 Year Opened: 1961 |
Henry Wise Wood High School is a public high school located at 910 75 Avenue Southwest, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education (CBE). The school originally opened in 1961, and was expanded in 1964, and renovated in 1976, 1998 and 2005. The fire alarm system was upgraded in 1997, and was fully replaced in 2022 due to a panel failure.
System Specifications (2022-present)
FACP
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the basement electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Annunciators
There is a Notifier LCD-160 annunciator next to the main office, in the main lobby.
Booster Panels
There are several Notifier ACPS-610 addressable power supplies throughout the school.
Notification Appliances
All classrooms, corridors and most other areas have System Sensor P2RLA horn/strobes (red, wall-mount, set to 15cd/electromechanical). Some areas have System Sensor SRLA remote strobes (red, wall-mount, set to 15cd) for additional visual coverage. The student washrooms have System Sensor P4RLA horn/strobes (red, wall-mount, set to 15cd), wired as remote strobes.
Initiating Devices
Pull Stations
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices
There are Notifier FSP-951A addressable photoelectric smoke detectors throughout the building, mounted on System Sensor B300A-6 bases. There may also be a sprinkler system installed, although this is unconfirmed.
System Specifications (1997-2022)
FACP
The building was protected by an Edwards EST2 addressable fire alarm system. The panel was located in the basement electrical room. The system ran Edwards’ Signature-series addressable protocol, and the system coding was continuous.
Notification Appliances
All notification appliances were General Signal MB10-24 motor bells (10” gong) mounted on Edwards 403-5A-R strobe plates (15cd).
Initiating Devices
Pull Stations
All pull stations were EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, and EST SIGA-HRS addressable fixed/rate-of-rise heat detectors in some areas. All detectors were mounted on EST SIGA-SB bases. [[Category:Facilitie]