Panorama Springs Lodge: Difference between revisions

From FireAlarmPedia
Line 17: Line 17:
There is an EST 2-LSRA-C remote annunciator at the main entrance.
There is an EST 2-LSRA-C remote annunciator at the main entrance.
==== Notification Appliances ====
==== Notification Appliances ====
All common area notification appliances except for one are General Signal MB10-24 motor bells (10" gong). There is an Edwards MB10-24 motor bell (10" gong) in the pool hallway installed around 2014 as a deficiency replacement. All units have General Signal 683-1C silenceable mini horns. For outdoor notification, there is a General Signal MB10-24 in the Panorama Springs Pools, mounted upside down under an overhang of the sauna.
 
===== Common Areas =====
All common area notification appliances except for one are General Signal MB10-24 motor bells (10" gong). There is an Edwards MB10-24 motor bell (10" gong) in the pool hallway installed around 2014 as a deficiency replacement.  
For outdoor notification, there is a General Signal MB10-24 in the Panorama Springs Pools, mounted upside down under an overhang of the sauna.
 
===== Units =====
The units have General Signal 683-1C silenceable mini horns.  


=== Initiating Devices ===
=== Initiating Devices ===
Line 26: Line 32:
===== Modules =====
===== Modules =====
There are EST SIGA-CT1 addressable modules supervising the building's sprinkler system flow and tamper switches.
There are EST SIGA-CT1 addressable modules supervising the building's sprinkler system flow and tamper switches.
== Bonus Information ==
== Bonus Information ==
The ground floor has a bell installed upside down, as well as the sauna. This is not a code violation, as the bells still output the required sound levels.
The ground floor has a bell installed upside down, as well as the sauna. This is not a code violation, as the bells still output the required sound levels.
[[Category:Facilities]]
[[Category:Facilities]]

Revision as of 21:01, 14 December 2023

System Specifications
FACP: Edwards EST2

FACP Location: Electrical Room
System Type:Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC

System Coding: Temporal?
Date of last known Upgrade: 2019-2020
Year Opened: 1999

Panorama Springs Lodge is a condo building located at 2080 Summit Drive, in Panorama Mountain Resort, British Columbia. It features the Panorama Springs Pools. It was built in 1999, and has the original fire alarm system, with parts replaced as deficiencies occur.

System Specifications (1999-present)

FACP

The building is protected by an Edwards EST2 addressable fire alarm system. The panel is located in an electrical room in the underground parking garage. The system runs EST's Signature addressable protocol, and the system coding is most likely temporal.

Annunciators

There is an EST 2-LSRA-C remote annunciator at the main entrance.

Notification Appliances

Common Areas

All common area notification appliances except for one are General Signal MB10-24 motor bells (10" gong). There is an Edwards MB10-24 motor bell (10" gong) in the pool hallway installed around 2014 as a deficiency replacement. For outdoor notification, there is a General Signal MB10-24 in the Panorama Springs Pools, mounted upside down under an overhang of the sauna.

Units

The units have General Signal 683-1C silenceable mini horns.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations. Most are original with the shield, but deficiency replacements of all generations starting with GE EST can be found scattered.

Automatic Detection Devices

The smoke detectors are EST SIGA-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases. Deficiency replacements of all generations can be found throughout. There is also a sprinkler system with waterflow.

Modules

There are EST SIGA-CT1 addressable modules supervising the building's sprinkler system flow and tamper switches.

Bonus Information

The ground floor has a bell installed upside down, as well as the sauna. This is not a code violation, as the bells still output the required sound levels.