All pull stations except for one were Edwards 275-C111 conventional pull stations. These were installed with the 6616, and were located at every exit, including an awkward install by a sliding glass door pointed toward the door handle. There was one original Edwards 270-SPO in the restaurant hallway exit. | All pull stations except for one were Edwards 275-C111 conventional pull stations. These were installed with the 6616, and were located at every exit, including an awkward install by a sliding glass door pointed toward the door handle. There was one original Edwards 270-SPO in the restaurant hallway exit. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There were Edwards 281C rate of rise/fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time. | There were Edwards 281C rate of rise/fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time. There was no sprinkler system. | ||
[[Category:Facilities]] | [[Category:Facilities]] |
Revision as of 12:46, 30 December 2023
System Specifications |
---|
FACP: Edwards 6616 (Inoperable) FACP Location: Entrance Hallway System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Date of last known Upgrade: 1989 Year Opened: 1978 Year Decommissioned: 2021 |
Raven Meadows Golf Resort is a golf course located in Alder Flats, AB at 454065 Highway 22. Its amenities include a campground an 18-hole golf course, and formerly a hotel with a restaurant and pro shop. This page will cover the former hotel. The resort was opened in 1978, and the hotel underwent a system upgrade in 1989 confirmed by the heat detectors. As of August 2021, the system was not inspected in 15 years, the panel had failed, and as a result, the system was inoperable. In October 2021, the hotel burnt down to the ground; the system did not activate for the fire. The system was last serviced in 2006.
System Specifications (1989-2021)
FACP
The hotel was protected by an Edwards 6616 conventional fire alarm system. The panel was located in the entrance hallway, and was installed in 1989. The system had three zones in use, and the system coding was continuous. As of August 2021, the panel suffered a main board failure, and was in stuck in alarm for all three zones plus an unused zone. Therefore, the system was no longer functional.
Notification Appliances
All notification appliances except one were Edwards 439D-10AWC vibrating bells (10” gong). The one in the lobby was vandalized; both labels removed, and the gong was mounted on the striker with a crosshead screw instead of the original hex bolt. In the hallway to the restaurant, there was an Edwards “Durabel” 6100D vibrating bell (10" gong), painted over with white to blend in with the wall, except for the label. All bells were installed in 1989.
Initiating Devices
Pull Stations
All pull stations except for one were Edwards 275-C111 conventional pull stations. These were installed with the 6616, and were located at every exit, including an awkward install by a sliding glass door pointed toward the door handle. There was one original Edwards 270-SPO in the restaurant hallway exit.
Automatic Detection Devices
There were Edwards 281C rate of rise/fixed-temperature heat detectors throughout the hotel. They were not replaced despite the recall due to the company being out of business by the time. There was no sprinkler system.