Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

St. Timothy High School: Difference between revisions

From FireAlarmPedia
mNo edit summary
Line 10: Line 10:
== System Specifications (2020-present) ==
== System Specifications (2020-present) ==
==== FACP ====
==== FACP ====
The school is protected by a Kidde VS4 fire alarm system. The panel is located in the caretaker's office, and was installed in spring 2020. The system runs Kidde's GSA addressable protocol, and the system coding is temporal. It took two whole months to install this system.  
The school is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the caretaker's office. The system runs Kidde's GSA addressable protocol, and the system coding is temporal. It took two whole months to install this system, starting in May 2020, and finishing in July.  
===== Annunciators =====
===== Annunciators =====
There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.
There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.
Line 20: Line 20:
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All of the pull stations are the original EST SIGA-270 addressable pull stations, which were installed during construction.
All pull stations are the original EST SIGA-270 addressable pull stations. These were kept from the previous system as they are compatible.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
The smoke detectors are Kidde KI-PD optical addressable smoke detectors. Certain rooms have Kidde KI-HD addressable rate-of-rise/fixed heat detectors. All detectors installed on KI-SB bases. The duct detectors in the air handling units and above ceilings are Kidde SD-2W two-wire photoelectric duct smoke detectors, connected to Kidde GSA-LED LED indicators. There is also a sprinkler system with waterflow.
The smoke detectors are Kidde KI-PD optical addressable smoke detectors. Certain rooms have Kidde KI-HD addressable rate-of-rise/fixed heat detectors. All detectors installed on KI-SB bases. The duct detectors in the air handling units and above ceilings are Kidde SD-2W two-wire photoelectric duct smoke detectors, connected to Kidde GSA-LED LED indicators. There is also a sprinkler system with waterflow.
Line 37: Line 37:


==== FACP ====
==== FACP ====
The school was formerly protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. It was installed in 2016 as an emergency replacement for the original QuickStart QS1 after a CPU failure. The system ran EST's Signature addressable protocol, and the system coding was temporal. The original QuickStart however was set to continuous. The system was replaced with the Kidde system in 2020.
The school was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. It was installed in 2016 as an emergency replacement for the original QuickStart QS1 after a CPU failure. The system ran EST's Signature addressable protocol, and the system coding was temporal. The original QuickStart however was set to continuous. The system was replaced with the Kidde system in 2020.
===== Annunciators =====
===== Annunciators =====
There was an EST QS1-CPU-1 annunciator at the entrance, and an SL30 card in it.
There was a QSA-1-S cabinet in the main entrance vestibule, with an EST QS1-CPU-1 CPU and an SL30 card in it.
==== Notification Appliances ====
==== Notification Appliances ====
The main notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R (15cd) strobe plates. These could also be found in the library, the music room, and even the changerooms. The gym and shop have louder ambient noise levels, and contained Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates. There were three in the gym.  
Most notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R (15cd) strobe plates. These could also be found in the library, the music room, and the changerooms. The gym and shop had Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates due to higher ambient noise levels. There were three in the gym, and two in the shop; one in the woodworking area and one in the main area.  


For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the hill where stairs to the basement are, in the staff parking lot, and in the tarmac. There is also an Edwards CS405-8A-T (110cd) weatherproof Integrity strobe installed in February 2020 as a deficiency replacement for the original EST one. The strobe is above the bike rack, and it is still in use on the Kidde system.
For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the front near the hill, one by the staff parking lot, and one at the tarmac. There was also an Edwards CS405-8A-T weatherproof strobe above the bike rack; this was installed in February 2020 as a deficiency replacement for the original EST one, and is still in use on the current system.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All of the pull stations were and still are the original EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.
All pull stations were EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
The smoke detectors were EST SIGA-PS addressable photoelectric smoke detectors, installed on EST SIGA-SB bases. Certain rooms such as the electrical room had EST SIGA-HRS addressable fixed/rate-of-rise heate detectors, also installed on SIGA-SB bases. Most were original, and some were deficiency replacements over the years. There were also EST SIGA-SD addressable photoelectric duct smoke detectors on the air handling units and behind the drop ceilings, indicated by EST SIGA-LED indicators. There was also a sprinkler system with waterflow detection.  
The smoke detectors were EST SIGA-PS addressable photoelectric smoke detectors. Certain rooms such as the electrical room had EST SIGA-HRS addressable fixed/rate-of-rise heat detectors. All detectors were mounted on SIGA-SB bases. Most were original, and some were deficiency replacements over the years. There were also EST SIGA-SD addressable photoelectric duct smoke detectors on the air handling units and behind the drop ceilings, indicated by EST SIGA-LED indicators. There was also a sprinkler system with waterflow detection.  
==== Modules ====
==== Modules ====
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches. There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches. There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.

Revision as of 16:40, 4 January 2024

System Specifications
FACP: Kidde VS4
FACP Location: Custodian's Office
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2020
Year Opened: 2004

St. Timothy High School is a junior and senior high school located at 501 Sunset Drive in the neighborhood of Sunset Ridge in Cochrane, AB. It was built in 2004, and the fire alarm system is from 2020. Only the pull stations are original.

System Specifications (2020-present)

FACP

The school is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the caretaker's office. The system runs Kidde's GSA addressable protocol, and the system coding is temporal. It took two whole months to install this system, starting in May 2020, and finishing in July.

Annunciators

There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.

Notification Appliances

The notification appliance circuits were mostly redone when the VS4 was installed.
All notification appliances except for one are from Edwards' "Genesis" line of products. The main notification appliances are Edwards GC-HDVM (white, ceiling, no FIRE marking, varies between 30 and 75cd) horn/strobes. There is one horn/strobe per classroom, and the library contains three horn/strobes. The open ceiling areas, such as the atrium, gymnasium, band/music room and the shop have Edwards G1R-HDVM (red, wall, no FIRE marking, varies between 15, 75, and 110cd) horn/strobes. The gym has two of the horn/strobes where the bell/strobes were, but the other two are in new locations, having two per side. In each washroom, there is an Edwards GC-VM (white, ceiling mount, no FIRE) remote strobe. All horn/strobes are set to high volume, and random candelas (mostly 75cd). Plates are covering where the bell/strobes were.

For exterior notification, there is an Edwards WG4RN-HVMC (red, no FIRE) weatherproof horn/strobe by the tarmac, and it is covered by a wire grill. There is also an Edwards "Integrity" CS405-8A-T weatherproof strobe by the bike rack that was installed in February 2020 when the QuickStart was still in service; the only notification appliance to remain from the previous system.
There used to be three outdoor bells, but when the Kidde system was installed, only one was replaced, and the other two locations are covered with metal plates.

Initiating Devices

Pull Stations

All pull stations are the original EST SIGA-270 addressable pull stations. These were kept from the previous system as they are compatible.

Automatic Detection Devices

The smoke detectors are Kidde KI-PD optical addressable smoke detectors. Certain rooms have Kidde KI-HD addressable rate-of-rise/fixed heat detectors. All detectors installed on KI-SB bases. The duct detectors in the air handling units and above ceilings are Kidde SD-2W two-wire photoelectric duct smoke detectors, connected to Kidde GSA-LED LED indicators. There is also a sprinkler system with waterflow.

Modules

There are Kidde GSA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches. There are also Kidde GSA-CR addressable control modules for shutting down the HVAC system and releasing the fire doors, wired to EST 1508-AQN5 magnetic door holders.

Former System Specifications (2004-2020)

Former System Specifications
FACP: EST QuickStart QS1
FACP Location: Custodian's Office
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: Feb 2020
Year Decomissioned: 2020


FACP

The school was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. It was installed in 2016 as an emergency replacement for the original QuickStart QS1 after a CPU failure. The system ran EST's Signature addressable protocol, and the system coding was temporal. The original QuickStart however was set to continuous. The system was replaced with the Kidde system in 2020.

Annunciators

There was a QSA-1-S cabinet in the main entrance vestibule, with an EST QS1-CPU-1 CPU and an SL30 card in it.

Notification Appliances

Most notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R (15cd) strobe plates. These could also be found in the library, the music room, and the changerooms. The gym and shop had Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates due to higher ambient noise levels. There were three in the gym, and two in the shop; one in the woodworking area and one in the main area.

For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the front near the hill, one by the staff parking lot, and one at the tarmac. There was also an Edwards CS405-8A-T weatherproof strobe above the bike rack; this was installed in February 2020 as a deficiency replacement for the original EST one, and is still in use on the current system.

Initiating Devices

Pull Stations

All pull stations were EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.

Automatic Detection Devices

The smoke detectors were EST SIGA-PS addressable photoelectric smoke detectors. Certain rooms such as the electrical room had EST SIGA-HRS addressable fixed/rate-of-rise heat detectors. All detectors were mounted on SIGA-SB bases. Most were original, and some were deficiency replacements over the years. There were also EST SIGA-SD addressable photoelectric duct smoke detectors on the air handling units and behind the drop ceilings, indicated by EST SIGA-LED indicators. There was also a sprinkler system with waterflow detection.

Modules

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches. There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.

List of known activations

September 21, 2020 - alarm at around 9:45 AM, activated by duct detector in air handling unit in gymnasium. Scent of smoke reported in gym and nearby areas prior to alarm. School was evacuated, Cochrane Fire Services responded and the cause was found to be a motor overheating, burning red hot and smoking from the electrical panel outputting 4x the rated current, due to FORTIS working on power. Alarm shut off after 30 minutes.

Gallery