Sheraton Syracuse University Hotel & Conference Center: Difference between revisions
More actions
(This system makes me want to never visit the City of Syracuse.) |
mNo edit summary |
||
Line 7: | Line 7: | ||
| FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2011 <br />Year Opened: 1984 | | FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2011 <br />Year Opened: 1984 | ||
|} | |} | ||
'''Sheraton''' is an American hotel chain owned by Marriott. The chain is headquartered in White Plains, New York, USA, and has franchises globally. This particular hotel is located at 801 University Avenue, in Syracuse, New York, USA. The hotel opened in 1984, and was renovated in 2011. The fire alarm system was upgraded in 2011. | |||
'''Sheraton''' is an American hotel chain owned by Marriott. | |||
==System Specifications (2011-present)== | ==System Specifications (2011-present)== | ||
====FACP==== | ====FACP==== | ||
The building is protected by an Edwards EST3 addressable fire alarm system. | The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The messages and/or tones are unknown at this time. | ||
=====Annunciators===== | =====Annunciators===== | ||
There is an Edwards EST3-LCDANN annunciator in the main lobby. | There is an Edwards EST3-LCDANN annunciator in the main lobby. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All notification appliances are Edwards “Integrity” 757-5A-SS70 speaker/strobes (red, wall-mount, 70V, 15cd). | All notification appliances are Edwards “Integrity” 757-5A-SS70 speaker/strobes (red, wall-mount, 70V, 15cd). | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are EST SIGA-278 addressable dual-action pull stations. | All pull stations are EST SIGA-278 addressable dual-action pull stations. | ||
====Automatic Detection Devices==== | |||
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building. These are mounted on EST SIGA-SB bases in common areas, and on EST SIGA-AB4G sounder bases in all guest rooms. There is also a sprinkler system with waterflow detection. | |||
==== | ==== Modules ==== | ||
There are EST SIGA- | There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches. |
Revision as of 12:36, 5 January 2024
System Specifications |
---|
FACP: Edwards EST3 FACP Location: Unknown System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: Unknown Strobes Synchronized: Yes, EST Date of last known Upgrade: 2011 Year Opened: 1984 |
Sheraton is an American hotel chain owned by Marriott. The chain is headquartered in White Plains, New York, USA, and has franchises globally. This particular hotel is located at 801 University Avenue, in Syracuse, New York, USA. The hotel opened in 1984, and was renovated in 2011. The fire alarm system was upgraded in 2011.
System Specifications (2011-present)
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The panel location is unknown. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The messages and/or tones are unknown at this time.
Annunciators
There is an Edwards EST3-LCDANN annunciator in the main lobby.
Notification Appliances
All notification appliances are Edwards “Integrity” 757-5A-SS70 speaker/strobes (red, wall-mount, 70V, 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-278 addressable dual-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building. These are mounted on EST SIGA-SB bases in common areas, and on EST SIGA-AB4G sounder bases in all guest rooms. There is also a sprinkler system with waterflow detection.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.