Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Best Western Plus Service Inn and Suites: Difference between revisions

From FireAlarmPedia
No edit summary
mNo edit summary
Line 5: Line 5:
|  
|  
|-
|-
| FACP: EST iO500  
| FACP: EST iO500
FACP Location: Main Entrance<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage:24VFWR
FACP Location: Main Entrance<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage:24VFWR


Line 12: Line 12:
Strobes Synchronized; Yes<br />Date of last known Upgrade: N/A <br />Year Opened: 2014
Strobes Synchronized; Yes<br />Date of last known Upgrade: N/A <br />Year Opened: 2014
|}
|}
'''Best Western''' is a large global hotel chain headquartered in Phoenix, Arizona. They have about 4,700 hotels worldwide. This particular hotel is located at 209 41 Street South, in Lethbridge, Alberta, Canada. The hotel opened in 2014, and the fire alarm system is original.
'''Best Western''' is a large global hotel chain headquartered in Phoenix, Arizona. They have about 4,700 hotels worldwide. This particular hotel is located at 209 41 Street South, in Lethbridge, Alberta, Canada. The hotel opened in 2014, and the fire alarm system is original.
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature-series addressable protocol, and the system coding is temporal.
The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.
====Notification Appliances====
====Notification Appliances====
All common areas have EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). All guest rooms have EST G1-HDVM horn/strobes (white, wall-mount, no lettering).
All common areas have EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). All guest rooms have EST G1-HDVM horn/strobes (white, wall-mount, no lettering).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are EST SIGA-270 addressable single-action pull stations.
All pull stations are EST SIGA-270 addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on EST SIGA-SB bases.
There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on EST SIGA-SB bases. There is no sprinkler system.
[[]

Revision as of 23:09, 18 January 2024

System Specifications
FACP: EST iO500

FACP Location: Main Entrance
System Type:Addressable
System Line Voltage: 120VAC
NAC Voltage:24VFWR

System Coding: Temporal

Strobes Synchronized; Yes
Date of last known Upgrade: N/A
Year Opened: 2014

Best Western is a large global hotel chain headquartered in Phoenix, Arizona. They have about 4,700 hotels worldwide. This particular hotel is located at 209 41 Street South, in Lethbridge, Alberta, Canada. The hotel opened in 2014, and the fire alarm system is original.

System Specifications

FACP

The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.

Notification Appliances

All common areas have EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd). All guest rooms have EST G1-HDVM horn/strobes (white, wall-mount, no lettering).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices

There are EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on EST SIGA-SB bases. There is no sprinkler system.