Line 43: | Line 43: | ||
FACP Location: In-portable<br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR | FACP Location: In-portable<br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR | ||
System Coding: Continuous<br />Date of last known Upgrade: | System Coding: Continuous<br />Date of last known Upgrade: Mid-1990s <br />Year Opened: 1988 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The portable is protected by an EST 6632 conventional fire alarm system. The panel replaced an Edwards 6602. The system coding is continuous. | The portable is protected by an EST 6632 conventional fire alarm system. The panel replaced an Edwards 6602, the cabinet remains beside it. The system coding is continuous. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
The notification appliances are Edwards 439D-10AWC vibrating bells (10" gong) | The notification appliances are Edwards 439D-10AWC vibrating bells (10" gong) |
Revision as of 18:55, 19 January 2024
System Specifications |
---|
FACP: Edwards Custom 6500
FACP Location: Mechanical Room likely on transformers.) System Coding: March Time |
Regina Mundi Catholic College is a catholic high school located at 5250 Wellington Rd S in London, Ontario. It was the second Catholic school to be built in Ontario. It was first built in 1963 as a seminary for boys, then an all boys school in 1967, and in 1983 added a gymnasium and science laboratories as a co-ed school. It was then expanded in 1988 as a high school. The fire alarm system was upgraded in 1988, but some of the bells and pull stations remain original.
There are also portables built between 1988 and 2000, which are independent from the main system, however all systems are wired to trip each other when one goes into alarm. The 2nd and 3rd floors were originally dorms, but were converted to classrooms.
System Specifications
FACP
The school is protected by an Edwards 6500 conventional fire alarm system. The panel is located in the mechanical room in the basement, and has an auxiliary panel for additional zones. It has a total of 52 zones. The 6500 was installed in 1988 after the major expansion, replacing an Edwards 1221T. The system coding is march time.
Annunciators
There is an annunciator for the Edwards 6500 located in the front foyer, model unknown.
Notification Appliances
Most of the notification appliances are the original Edwards "Adaptabel" model 23 single-stroke bells (10" gong, 4VDC) The library and cafeteria have one original Edwards model 23 bell each, as well as one Edwards 439D-10AWC (10" gong) vibrating bell, installed during the 1988 renovation. In the double gymnasium added in 1988, there are Edwards 439D-10AWC vibrating bells (10" gong).
In the science wing, there is one original Edwards bell, and an Edwards "Adaptabel" 333D single-stroke bell (10" gong) installed as a deficiency replacement. The music room also has an Edwards 439D-10AWC bell, and in the hallway outside of it, an Edwards "Adaptabel" model 24 single-stroke bell (10" gong, 12VAC).
The 4VDC and 12VAC bells are wired to transformers to operated off 24VDC, located directly behind the bells.
Technology Wing (1988)
There is an Edwards 439D-6AWC vibrating bell (6" gong) in a hallway, and Edwards 439D-10AWC vibrating bells (10", including one in a storage room due to that part being formerly being a hallway.
Initiating Devices
Pull Stations
Most of the pull stations are the original first generation Edwards 270-SPO pull stations. In the 1988 parts, there are newer Edwards 270A-SPO pull stations. The tech wing, however has a few Mirtone 73201 dual-action pull stations.
Automatic Detection Devices
There are Edwards 6250C ionization smoke detectors and Edwards 281C rate-of-rise/fixed-temperature heat detectors located throughout the school, installed in 1988. There is an original Edwards 241 rate-of-rise/fixed heat detector behind the chapel. There is also a System Sensor 2151A photoelectric smoke detector mounted on a B114LPA base, installed as a deficiency replacement.
System Specifications (English and Dance Portables)
System Specifications |
---|
FACP: EST 6632
FACP Location: In-portable System Coding: Continuous |
FACP
The portable is protected by an EST 6632 conventional fire alarm system. The panel replaced an Edwards 6602, the cabinet remains beside it. The system coding is continuous.
Notification Appliances
The notification appliances are Edwards 439D-10AWC vibrating bells (10" gong)
Initiating Devices
Pull Stations
The pull stations are Edwards 270-SPO pull stations.
Automatic Detection Devices
All smoke detectors are Edwards 6250C ionization smoke detectors.
System Specifications (Religion Portable)
System Specifications |
---|
FACP: Mircom FA-101T
FACP Location: In-Portable System Coding: Temporal |
FACP
The portable is protected by a Mircom FA-101T conventional fire alarm system. The panel replaced an older Edwards panel in the 2000s. The system coding is temporal.
Notification Appliances
The notification appliances are Mircom BL-6B motor bells (6" gong)
Initiating Devices
Pull Stations
The pull stations are Mircom MS-401 pull stations in the hallways, and Edwards 275-C111 pull stations in the classes, leftover from the previous system.
Automatic Detection Devices
None noticed.