Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST3X <br /> FACP Location: Main Lobby by Escalators <br />System Type: Addressable, Two-Stage <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (First Stage) <br> Temporal (GA) <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2017 <br />Year Opened: 2001
| FACP: Edwards EST3X <br /> FACP Location: Main Lobby by Escalators <br />System Type: Addressable, Two-Stage <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (Alert)<br> Temporal (Alarm)<br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2017 <br />Year Opened: 2001
|}
|}
'''Scotiabank Theatre''' is a theatre chain owned by Cineplex. This particular theatre is located at 6455 Macleod Trail Southwest, in Calgary, Alberta, Canada. The theatre is attached to [[CF Chinook Centre]], however the fire alarm systems are not connected. The theatre opened in 2001, following the large expansion and renovation of the mall. The fire alarm system is original with the exception of the FACP and smoke detectors.
'''Scotiabank Theatre''' is a theatre chain owned by Cineplex. This particular theatre is located at 6455 Macleod Trail Southwest, in Calgary, Alberta, Canada. The theatre is attached to [[CF Chinook Centre]], however the fire alarm systems are not connected. The theatre opened in 2001, following the large expansion and renovation of the mall. The fire alarm system is original with the exception of the FACP and smoke detectors.
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main lobby, to the left of the escalators. The system runs EST’s Signature-series addressable protocol, and is configured for two-stage operation. First stage coding is 20BPM, followed by temporal in general alarm. This panel replaced an Edwards EST3, of which the cabinet remains, and is used as a junction box.
The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main lobby, to the left of the escalators. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal in for the alarm coding. This panel replaced an Edwards EST3, of which the cabinet remains, and is used as a junction box.
=====Annunciators=====
=====Annunciators=====
There is an Edwards EST3-LCDANN annunciator near the west entrance.
There is an Edwards EST3-LCDANN annunciator near the west entrance.
Line 20: Line 20:
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.
There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches. There are also EST SIGA-CR addressable relays serving various purposes.
[[Category:Facilities]]
[[Category:Facilities]]

Revision as of 00:58, 28 January 2024

System Specifications
FACP: Edwards EST3X
FACP Location: Main Lobby by Escalators
System Type: Addressable, Two-Stage
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes
Date of last known Upgrade: 2017
Year Opened: 2001

Scotiabank Theatre is a theatre chain owned by Cineplex. This particular theatre is located at 6455 Macleod Trail Southwest, in Calgary, Alberta, Canada. The theatre is attached to CF Chinook Centre, however the fire alarm systems are not connected. The theatre opened in 2001, following the large expansion and renovation of the mall. The fire alarm system is original with the exception of the FACP and smoke detectors.

System Specifications

FACP

The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the main lobby, to the left of the escalators. The system runs EST’s Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, followed by temporal in for the alarm coding. This panel replaced an Edwards EST3, of which the cabinet remains, and is used as a junction box.

Annunciators

There is an Edwards EST3-LCDANN annunciator near the west entrance.

Notification Appliances

All notification appliances are Edwards 439D-10AWC vibrating bells (10” gong) on EST 403-5A-R strobe plates (15cd).

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices

There are Edwards SIGA-PD addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches. There are also EST SIGA-CR addressable relays serving various purposes.