The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located just past the main entrance. The system runs Simplex’s IDNet addressable initiating and IDNAC addressable signaling protocols, and is equipped with voice evacuation. The messages and/or tones are unknown at this time. | The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located just past the main entrance. The system runs Simplex’s IDNet addressable initiating and IDNAC addressable signaling protocols, and is equipped with voice evacuation. The messages and/or tones are unknown at this time. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All indoor notification appliances are Simplex “TrueAlert ES” 49SVH-APPLC-O addressable speaker/strobes fitted with 49SVC-CWFIRE-O covers(white, ceiling-mount, set to 15cd). In the stairways, there are Simplex "TrueAlert" 4902-9721 (ceiling mount, 70V) speakers on every second floor. For outdoor notification, there is a Simplex 49SVH-APPLW-O weatherproof addressable speaker/strobe (red, wall-mount) outside the main entrance, fitted with a 49SVC-WRFIRE-O cover. | All indoor notification appliances are Simplex “TrueAlert ES” 49SVH-APPLC-O addressable speaker/strobes fitted with 49SVC-CWFIRE-O covers(white, ceiling-mount, set to 15cd). | ||
In the stairways, there are Simplex "TrueAlert" 4902-9721 (ceiling mount, 70V) speakers on every second floor. | |||
For outdoor notification, there is a Simplex 49SVH-APPLW-O weatherproof addressable speaker/strobe (red, wall-mount) outside the main entrance, fitted with a 49SVC-WRFIRE-O cover. | |||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== |
Revision as of 14:37, 2 February 2024
System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 29VDC (Visual) System Coding: Unknown Strobes Synchronized: Yes, IDNAC Date of last known Upgrade: 2020s Year Opened: 1962 |
The University of Alberta is a public research university located in Edmonton, Alberta, Canada. This page will cover Henry Kelsey Hall, which opened in 1962. The fire alarm system was upgraded in 2020.
System Specifications (2020-present)
FACP
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located just past the main entrance. The system runs Simplex’s IDNet addressable initiating and IDNAC addressable signaling protocols, and is equipped with voice evacuation. The messages and/or tones are unknown at this time.
Notification Appliances
All indoor notification appliances are Simplex “TrueAlert ES” 49SVH-APPLC-O addressable speaker/strobes fitted with 49SVC-CWFIRE-O covers(white, ceiling-mount, set to 15cd).
In the stairways, there are Simplex "TrueAlert" 4902-9721 (ceiling mount, 70V) speakers on every second floor.
For outdoor notification, there is a Simplex 49SVH-APPLW-O weatherproof addressable speaker/strobe (red, wall-mount) outside the main entrance, fitted with a 49SVC-WRFIRE-O cover.
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases. The building is equipped with a sprinkler system.
Modules
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.