Winfield Agriplex: Difference between revisions

From FireAlarmPedia
(→‎Pull Stations: updated pull statoin info. lots of deficiencies (missed some devices))
mNo edit summary
Line 5: Line 5:
|  
|  
|-
|-
| FACP: EST 6601 (Inoperable) <br />FACP Location: Lobby, Hall Side <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br />Date of last known Upgrade: Mid-1990s <br />Year Opened: 1970s?
| FACP: EST 6601 <br />FACP Location: Lobby, Hall Side <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br />Date of last known Upgrade: Mid-1990s <br />Year Opened: 1970s?
|}
|}
'''Winfield Arena''' is an arena, located at 401 6 St E, Wetaskiwin County, AB. It was built in the 1970s, and the fire alarm system is most likely original except for the panel. The system will likely be upgraded this year.
'''Winfield Arena''' is an arena, located at 401 6 St E, Wetaskiwin County, AB. It was built in the 1970s, and the fire alarm system is most likely original except for the panel. The system will likely be upgraded this year.
== System Specifications (1970s-present) ==
== System Specifications (1970s-present) ==
''NOTE: This system is pending further investigation. This page should not be used for official purposes.''
''NOTE: This system is pending further investigation. This page should not be used for official purposes.''
==== FACP ====
==== FACP ====
The building is protected by an EST 6601 conventional fire alarm system. The panel is located in the lobby, on the hall side, and is also noticeably mounted high. The system coding is continuous.  
The building is protected by an EST 6601 conventional fire alarm system. The panel is located in the lobby, on the hall side, and is also noticeably mounted high. The system coding is continuous.  
Line 18: Line 17:
==== Pull Stations ====
==== Pull Stations ====
Most pull stations are Sentron 303 conventional pull stations. <br> There are some Sentron 304 conventional two-stage pull stations, wired as single-stage.
Most pull stations are Sentron 303 conventional pull stations. <br> There are some Sentron 304 conventional two-stage pull stations, wired as single-stage.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
Most heat detectors are Edwards 281C rate-of-rise/fixed heat detectors.  
Most heat detectors are Edwards 281C rate-of-rise/fixed heat detectors.  


There is an FDD CR135 fixed-temperature heat detector in the Olympia Room as a deficiency replacement. There is no sprinkler system.
There is an FDD CR135 fixed-temperature heat detector in the Olympia Room as a deficiency replacement. There is no sprinkler system.

Revision as of 23:46, 10 February 2024

System Specifications
FACP: EST 6601
FACP Location: Lobby, Hall Side
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Continuous
Date of last known Upgrade: Mid-1990s
Year Opened: 1970s?

Winfield Arena is an arena, located at 401 6 St E, Wetaskiwin County, AB. It was built in the 1970s, and the fire alarm system is most likely original except for the panel. The system will likely be upgraded this year.

System Specifications (1970s-present)

NOTE: This system is pending further investigation. This page should not be used for official purposes.

FACP

The building is protected by an EST 6601 conventional fire alarm system. The panel is located in the lobby, on the hall side, and is also noticeably mounted high. The system coding is continuous.

Notification Appliances

All notification appliances are Chubb 960-1032 vibrating bells (10” gong). There is also one installed outdoors for exterior notification.

Initiating Devices

Pull Stations

Most pull stations are Sentron 303 conventional pull stations.
There are some Sentron 304 conventional two-stage pull stations, wired as single-stage.

Automatic Detection Devices

Most heat detectors are Edwards 281C rate-of-rise/fixed heat detectors.

There is an FDD CR135 fixed-temperature heat detector in the Olympia Room as a deficiency replacement. There is no sprinkler system.