Sheraton Arlington Hotel: Difference between revisions

From FireAlarmPedia
(Chase sucks)
 
Line 32: Line 32:
==== Modules ====
==== Modules ====


There are Silent Knight IDP addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Silent Knight IDP-MONITOR addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

Revision as of 13:06, 11 February 2024

System Specifications
FACP: Silent Knight IFP-1000 VIP
FACP Location: Unknown
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (audible)
24VDC (visual)
System Coding: Unknown
Strobes Synchronized:Yes, Wheelock
Date of last known Upgrade: 2009
Year Opened: 1984

Sheraton Arlington Hotel is a 4-star hotel located at 1500 Convention Center Dr, Arlington, Texas. It has 310 rooms. It was built in 1984, and was renovated in 2009. The fire alarm system was installed during the renovation.

System Specifications (2009-present)

FACP

The building is protected by a Silent Knight IFP-1000 VIP addressable fire alarm system. The panel location is unknown. The system runs Silent Knight’s SD addressable protocol, and is equipped with voice-evacuation.

Notification Appliances

The notification appliances are a mix of Wheelock E70-24MCW speaker/strobes (red, wall-mount, set to 15cd) and Wheelock E90-24MCC-FW speaker/strobes (white, ceiling mount, set to 75cd).

Initiating Devices

Pull Stations

All pull stations are Silent Knight SD500-PS addressable single-action pull stations.

Automatic Detection Devices

There are Silent Knight SD505-APS addressable photoelectric smoke detectors located throughout the hotel. There is also a sprinkler system with waterflow detection.

Modules

There are Silent Knight IDP-MONITOR addressable monitor modules supervising the sprinkler system’s tamper and flow switches.